94
The black square (
■
) indicates a switch position.
1
ON OFF
2
3
4
5
6
7
8
1
ON OFF
2
3
4
5
6
<Initial settings>
Switch
Step
Function
Operation in Each Switch Setting
Remarks
Purpose
Additional Information
ON
OFF
When to Set
SW5 function switch
7
During the outdoor unit is in HEA
T
operation, slightly opens the electronic expansion valve on the indoor unit which is in F
AN, ST
OP
, COOL
or thermo-OFF*
3
Active
Inactive
Can be set when OFF or during operation
To open the LEV opening higher for units other than in
HE
AT
operation.
To avoid a r
efr
iger
ant shor
tage (
less
capacity)
due to refriger
ant liquid accumulation in the
units which is not in operation.
A
refrigerant
flow
noise
might
be
gene
rated
in units other than the one in operation.
8
During the outdoor unit is in operation, fully opens the electronic expansion valve on the indoor unit which is in FAN, COOL, ST
OP
, or thermo-OFF
.*
4
Enable
Normal
Can be set when OFF or during operation
To reduce the room temperature increase by setting the LEV opening lower for the units in thermo-OFF
operation.
The refrigerant is more likely to collect in the units with thermo-OFF operation, and causing the units refrigerant shortage. (Results in less capacity and increase of discharge temperature.)
SW6 function switch
1
—
—
—
—
<Initial settings>
—
—
2
—
—
—
—
—
—
3
—
—
—
—
—
—
4
Change of defrosting control
Enable (For high humidity)
Normal
Can be set when OFF or during operation
To shorten the defrosting prohibition time in high humidity (or heavy snow) region, in order to reduce malfunctions caused by frost .
The performance of the HEA
T operation is somewhat
reduced since the defrosting operation is frequently performed.
5
Ignore
refrigerant
filling
abnormality
Enable
Normal
To ignore the error detection of excessive charge of refrigerant.
The unit can be excessively charged w
ith
refrigerant depending on the operating condition.
Make sure that the unit is not excessively charged with refrigerant before starting operation when servicing or installing the units.
6
Switching the target discharge pressure (Pdm)
Enable
Normal
To raise the performance by setting the PDm higher during HEA
T operation.
Power consumption is raised due to a higher frequency
. (The performance would not be raise at the
maximum operating frequency
.)
7
Switching (1) the target evaporation temperature (ETm)
Enable
Normal
To raise/reduce the performance by changing the target ETm during COOL
operation.
Switch to raise the performance: raises the performance Switch to reduce the performance: prevents dew condensation
Switching it to raise the performance, it raises the power
consumption, and produces more dew condensation. Switching it to reduce the performance, it makes the
performance insufficient.
8
Switching (2) the target evaporation temperature (ETm)
Enable
Normal
SW7 function switch
1
Ignore current sensor abnormality
Enable
Normal
After turning the power ON.
<Initial settings>
To perform a test run for electrical parts alone without running the compressor
.
Make sure to connect the connector
s to the compr
essor
after checking the electrical parts.Be careful not to get electrical shock while working on electrical parts.
2
Setting the energization of base
heater
Limited run
Normal
Anytime
To set the energization of base heater
.
ON: Energizing only when the unit is in HEA
T operation.
OFF: Energizing while the HEA
T operation is stopped.
3
—
—
—
—
—
—
4
—
—
—
—
—
—
5
—
—
—
—
—
—
6
Forced defrost
Forced defrost
Normal
During compressor running in HEA
T
mode.
Turn ON when it is necessary to perform the defrosting operation forcedly
.
(
Ef
fective only at start-up, or 10
minutes after the last defrosting operation)
It performs the defrosting operation forcedly
.
(HEA
T operation is stopped temporarily
.)
SW9 Function Switch
1
—
—
—
—
<Initial settings>
—
—
2
—
—
—
—
—
—
*
3
SW5-7 Opens the indoor-
electronic
expancion valve as a countermeasure against the indoor unit in F
AN, COOL, ST
OP
, or thermo-OFF operation with refrigerant-shortage status due to an accumulation of liquid refrigerant
in the indoor unit. *
4
SW5-8 Countermeasure against room temperature rise for indoor unit in F
AN, COOL, and thermo-OFF (heating) mode.
1
ON OFF
2
3
4
5
6
SW6-6
OFF
ON
Target Pdm (kg/cm²)
29.5
31.5
SW6-7
OFF
ON
OFF
ON
SW6-8
OFF
OFF
ON
ON
Target ETm (
:
)
9
11
6
14
1
ON OFF
2
3
4
OCH575