22
• Name, Symbol, and the Maximum Units for Connection
Permissible
Length
Prohibited
items
• Longest length via outdoor units : L
1
+L
2
+L
3
+L
4,
L
1
+L
2
+L
3+
L
5,
L
1
+L
2
+L
6
+L
7
[
500 meters (1.25mm²)
• Longest transmission cable length : L
1,
L
3
+L
4
, L
3+
L
5
, L
6,
L
2
+L
6
, L
7
[
200 meters (1.25mm²)
• Remote controller cable length :
R
1
,
R
2
,
R
2
+
R
3
,
R
4
[
10 meters (0.5 to 1.25mm²)
If the length exceeds 10 meters, use a 1.25 mm² shielded wire. The length of this sec-
tion (L
8
) should be included in the calculation of the maximum length and overall length.
• Never connect together the terminal blocks (TB5) for transmission wires for indoor units (IC) that have been connected to
different outdoor units (OC).
• Set all addresses to ensure that they are not overlapped.
• M-NET remote controller and MA remote controller cannot be connected with the indoor unit of the same group wiring
together.
A
B
C
E
D
IC
(51)
TB5
RC
(01)
IC
TB5
(03)
IC
TB5
(02)
IC
TB5
(04)
IC
TB5
(05)
IC
TB5
(07)
IC
TB5
(06)
(101)
RC
(105)
RC
(104)
RC
(155)
OC
(53)
OC
Power Supply
Unit
A
: Group
B
: Group
C
: Group
D
: Shielded Wire
E
: Sub Remote Controller
( ): Address example
TB7
TB3
M1 M2 S
TB7
M1 M2 S
M1 M2 S
TB3
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
M1 M2 S
A B
A B
A B
A B
M1 M2 S
System
controller
D
NO
NO
OCH575