16
6
ACL4
CNCT
(RED)
CNAC2
(RED)
CNAC1
(WHT)
GD2
BLK
WHT
WHT
CNDC
(PNK)
CNL
(BLU)
1
3
1
3
1
3
2
1
3
1 2
+
-
+
BLK
BLU
WHT
RED
BLK
WHT
RED
LI1
POWER
SUPPLY
3N~
400V 50Hz
LI2
LI3
NI
TB1
L1
L2
L3
N
GD1
BLK
LO1
LO2
LO3
GRN/YLW
RED
RED
YLW
YLW
P. B.
N. F.
WHT
U
V
W
SC-U
SC-V
SC-W
RED
MS
3~
TB-L1
TB-L2
TB-L3
M1
M2
S
TB3
TO INDOOR UNIT
CONNECTING WIRES
DC 30V(Non-polar)
FOR CENTRALIZED
CONTROL
DC 30V(Non-polar)
M1
M2
S
TB7
2
2
2
2
2
CN51
(WHT)
SW2
SW8
SW1
SW7
SW3
SW4
SWU2 SWU1
TRANS
LED1
CN2
(RED)
CN4
(WHT)
LED3
CN3D
(WHT)
CN3S
(RED)
CN3N
(BLU)
CN1
(WHT)
TB1
CNDC
(PNK)
t°
t°
t°
t°
MF1
MS
3~
LEV-B
M
1
4
1
3
1
7
3
1 3 1 3 1 3
3
1
1
2
2
2
1 1
1 2
1 2
2
2 1 2 1
2
3
1
2
1
TH7 TH6 TH3 TH4
63HS
63H
CNF1
(WHT)
MF2
MS
3~
1
7
1
7
7
1
5
1
5
CNF2
(WHT)
TH7/6
(RED)
CNLVB
(RED)
TH3
(WHT)
TH4
(WHT)
1
CN5
(RED)
t°
TH2
TH2
(BLK)
63HS
(WHT)
1 3
1 3
63LS
63LS
(BLU)
63H
(YLW)
MULTI. B.
LED2
M-NET P.B.
52C
(BLK)
3
1
3
1
3
1
X505
21S4
(GRN)
SV1
(GRY)
SV2
(BLU)
SS
(WHT)
21S4
SV1
CNAC
(RED)
CNS1
(RED)
CNS2
(YLW)
F1
F2
X504
X503
X502
X501
CN102
(WHT)
CN2
(WHT)
4
4
1
1
CN40
(WHT)
4
1
5 3 1
CN41
(WHT)
4
1
4
2
RED
RS
BLK
WHT
WHT
RED
RED
BLK
BLK
BLK
BLK
TB-P2 TB-C1 TB-N1
TH8
CB1
CB2
TB-P1
CN4
(WHT)
CN2
(WHT)
1
2
7
7
2
1
2
2
2
2
-
-
+
+
+
+
+
is the switch position.
LEV-A
M
1
5
CNLVA
(WHT)
DCL
MC
SW6
SW5
SW9
X52A
+
t°
MODELS
PUMY-P200YKM
SW4
SW8
*1 MODEL SELECTION
The black square ( ) indicates a switch position.
ON
OFF
1 2 3 4 5 6
ON
OFF
1 2
1 2 3 4 5 6 7 8
[Example]
When the compressor and
SV1 are turned during cooling
operation.
RS
Rush Current Protect Resistor
ConnectionTerminal<Electrical Parts Box>
GD1,GD2
N.F.
Connection Terminal<L1/L2/L3-Power Supply>
Noise Filter Circuit Board
LI1/LI2/LI3/NI
Connection Terminal<L1/L2/L3-Power Supply>
LO1/LO2/LO3
SYMBOL
NAME
TB1
Terminal Block <Power Supply>
TB3
TB7
Terminal Block
<Centralized Control Transmission Line>
Terminal Block
<Indoor/Outdoor Transmission Line>
MC
Motor For Compressor
MF1,MF2
Fan Motor
CB1,CB2
Main Smoothing Capacitor
LEV-A,LEV-B Electronic Expansion Valve
21S4
Solenoid Valve<Four-Way Valve>
SV1
Solenoid Valve<Bypass valve>
TH3
Thermistor<Outdoor Liquid Pipe>
TH2
Thermistor<Hic Pipe>
TH4
Thermistor<Compressor>
TH6
Thermistor<Suction Pipe>
TH7
TH8
Thermistor<Ambient>
Thermistor<Heat Sink>
63H
High Pressure Switch
63HS
High Pressure Sensor
63LS
Low Pressure Sensor
ACL4
Reactor
DCL
P.B.
Power Circuit Board
Connection Terminal<U/V/W-Phase>
TB-U/V/W
MULTI.B.
Fuse<T6,3AL250V>
F1,F2
Switch<Display Selection>
SW1
Switch<Function Selection>
SW2
Switch<Test Run>
SW3
Switch<Model Selection>
SW4
Switch<Function Selection>
SW5
Switch<Function Selection>
SW6
Switch<Function Selection>
SW7
Switch<Model Selection>
SW8
Switch<Function Selection>
SW9
Switch<Unit Address Selection, unit digit>
SWU1
Switch<Unit Address Selection, tens digit>
SWU2
LED<Operation Inspection Display>
LED1,LED2
LED<Power Supply to Main Microcomputer>
LED3
Multi Controller Circuit Board
Connector<Connection For Option>
SS
Connector<Connection For Option>
CN3D
Connector<Connection For Option>
CN3S
Connector<Connection For Option>
CN3N
Connector<Connection For Option>
CN51
Relay
X501~505
M-NET P.B.
ConnectionTerminal<Electrical Parts Box>
M-NET Power Circuit Board
TB1
Connection Terminal<L1/L2/L3-Power Supply>
TB-L1/L2/L3
Connection Terminal
TB-P1/P2/C1/N1
Connection Terminal
SC-W/V/U
52C Relay
X52A
Reactor
Connector<Indoor/Outdoor Transmission Line>
CNS1
Connector<Centralized Control Transmission Line>
CNS2
Bit
Indication
1
Compressor
operated
2
52C
3
21S4
4
SV1
5
(SV2)
-
-
6
7
8
Always lit
●
During normal operation
The LED indicates the drive state of the controller in the outdoor unit.
●
When fault requiring inspection has occurred
The LED alternately indicates the inspection code and the location of the unit in which
the fault has occurred.
NOTES:
1.Refer to the wiring diagrams of the indoor units for details on wiring of each indoor unit.
Self-diagnosis function
The indoor and outdoor units can be diagnosed automatically using the self-diagnosis switch
(SW1) and LED1, LED2 (LED indication) found on the multi-controller of the outdoor unit.
LED indication : Set all contacts of SW1 to OFF.
Cautions when Servicing
!
●
WARNING: When the main supply is turned off, the voltage [570 V] in the main capacitor will drop to 20 V in approx. 5
minutes (input voltage: 400 V). When servicing, make sure that LED1, LED2 on the outdoor circuit board goes out, and then
wait for at least 5 minute.
●
Components other than the outdoor board may be faulty: Check and take corrective action, referring to the service manual.
Do not replace the outdoor board without checking.
WIRING DIAGRAM
PUMY-P200YKM PUMY-P200YKM-BS
OCH575