Check code
1302
High pressure trouble
●Diagnosis of defectives
Make sure to turn the power OFF before connecting/disconnecting any connectors, or replacing boards.
Diagnosis
Remedy
Chart 4 of 4
No
No
Yes
Continued from the previous page
Is there a voltage detected?
Replace the SV1.
Replace the 63HS.
Replace outdoor multi controller circuit
board.
Yes
No
<63H equipped model (63HS non-equipped)>
<63HS equipped model (63H non-equipped)>
Is the connector for outdoor
multi controller circuit board 63H
disconnected or loose?
Reconnect the connector or connect it tightly.
Replace the outdoor multi controller circuit
board.
Check the 63HS voltage.
Is there a resistance detected?
Yes
38