60
OCH665B
The black square ( ) indicates a switch position.
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Indoor room temperature (TH1)
8–39
8–39
°C
1
ON
2 3 4 5 6
Indoor pipe temperature/Liquid
(TH2)
Indoor
−39–88
−39–88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
1
ON
2 3 4 5 6
Indoor pipe temperature/Cond./
Eva. (TH5)
Indoor
−39–88
−39–88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
1
ON
2 3 4 5 6
Outdoor liquid pipe temperature
(TH3)
−40–90
−40–90
(When the coil thermistor detects 0°C or below, “–”
and temperature are displayed by turns.)
(Example) When −10°C;
0.5 s 0.5 s 2 s
10
°C
1
ON
2 3 4 5 6
Discharge temperature (TH4)
3–186
3–186
(When the discharge thermistor detects 100°C or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105°C;
0.5 s 0.5 s 2 s
1
05
°C
1
ON
2 3 4 5 6
Outdoor 2–phase pipe temperature (TH6)
−40–90
(When the coil thermistor detects 0°C or below, “–”
and temperature are displayed by turns.)
(Example) When −10°C;
0.5 s 0.5 s 2 s
10
°C
1
ON
2 3 4 5 6
Outdoor temperature (TH7)
−39–88
−39–88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
1
ON
2 3 4 5 6
Outdoor heat sink temperature
(TH8)
−40–186
−40–186
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the thermistor detects 100°C or more, hundreds
digit, tens digit and ones digit are displayed by turns.)
°C
1
ON
2 3 4 5 6
Comp. surface temperature (TH33) 3–217
(When the discharge thermistor detects 100°C or
more, hundreds digit, tens digit and ones digit are
displayed by turns.)
(Example) When 105°C;
0.5 s 0.5 s 2 s
1
05
°C