61
OCH665B
The black square ( ) indicates a switch position.
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
FTC pipe temperature/liquid (TH2)
−39–88
−39–88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
1
ON
2 3 4 5 6
Outdoor pressure sensor satu-
rated temperature (63HS)
−39–88
−39–88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
°C
1
ON
2 3 4 5 6
Discharge superheat SHd
0–186
TH4 − 63HS
0–186
(When the temperature is 100°C or more, hundreds digit,
tens digit and ones digit are displayed by turns.)
°C
1
ON
2 3 4 5 6
Sub cool
0–130
Cooling: 63HS–TH3
Heating: 63HS–TH2
DHW, Cooling & DHW: 63HS–TH34
Heating & DHW: "63HS–TH2" or
"63HS–TH34", whichever is lower.
0–130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
°C
1
ON
2 3 4 5 6
Compressor operating frequency
0–255
0– 255
(When it is 100Hz or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 125Hz;
0.5 s 0.5 s 2 s
1
25
Hz
1
ON
2 3 4 5 6
LEV-A opening pulse
0–480
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.
(Example) When 150 pulse;
0.5 s 0.5 s 2 s
1
50
Pulse
1
ON
2 3 4 5 6
LEV-B opening pulse
0–480
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 s 0.5 s 2 s
30
1
Pulse
1
ON
2 3 4 5 6
LEV-C opening pulse
0–480
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 s 0.5 s 2 s
30
1
Pulse
1
ON
2 3 4 5 6
Compressor operating current
0–50
0–50
Note: Omit the figures after the decimal fractions.
A