66
OCH665B
The black square ( ) indicates a switch position.
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Outdoor heatsink temperature
(TH8) on error occurring
−40–186
−40–186
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(When the temperature is 100°C or more, hundreds digit,
tens digit and ones digit are displayed by turns.)
°C
1
ON
2 3 4 5 6
Outdoor pressure sensor satu-
rated temperature (63HS) on error
occurring
−39–88
−39–88
(When the temperature is 0°C or less, “–” and
temperature are displayed by turns.)
(Example) When –15°C;
0.5 s 0.5 s 2 s
15
°C
1
ON
2 3 4 5 6
Discharge superheat on error
occurring
SHd
0–186
TH4 − 63HS
0–186
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 150°C;
0.5 s 0.5 s 2 s
50
1
°C
1
ON
2 3 4 5 6
Sub cool on error occurring SC
0–130
Cooling: 63HS–TH3
Heating: 63HS–TH2
DHW, Cooling & DHW: 63HS–TH34
Heating & DHW: "63HS-TH2" or
"63HS-TH34", whichever is lower.
0–130
(When the temperature is 100°C or more, hundreds
digit, tens digit and ones digit are displayed by
turns.)
(Example) When 115°C;
0.5 s 0.5 s 2 s
15
1
°C
1
ON
2 3 4 5 6
Operation frequency on error
occurring
0–255
0–255
(When it is 100 Hz or more, hundreds digit, tens digit and
ones digit are displayed by turns.)
(Example) When 125 Hz;
0.5 s 0.5 s 2 s
25
1
Hz
1
ON
2 3 4 5 6
LEV-A opening pulse on error
occurring
0–480
0–480
(When it is 100 pulse or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
(Example) When 130 pulse;
0.5 s 0.5 s 2 s
30
1
Pulse
1
ON
2 3 4 5 6
Compressor operating current on
error
occurring
0–50
0–50
A
1
ON
2 3 4 5 6
Fan step on error occurring
0–10
0–10
Step