62
OCH665B
The black square ( ) indicates a switch position.
SW2 setting
Display detail
Explanation for display
Unit
1
ON
2 3 4 5 6
Input current of outdoor unit
0–500
(When it is 100 or more, hundreds digit, tens digit
and ones digit are displayed by turns.)
0.1 A
1
ON
2 3 4 5 6
DC bus voltage
180–380
180–380
(When it is 100 V or more, hundreds digit, tens
digit and ones digit are displayed by turns.)
V
1
ON
2 3 4 5 6
Output step of outdoor FAN
0–10
0–10
Step
1
ON
2 3 4 5 6
Sub cool step
1–5
Step
1
ON
2 3 4 5 6
FTC ∆tj
0–99
Code
1
ON
2 3 4 5 6
ATA ∆tj
0–99
Code
1
ON
2 3 4 5 6
Indoor setting temperature
10–30
10–30
:
1
ON
2 3 4 5 6
The number of connected indoor
units
0–2
(The number of connected indoor units are displayed.)
Unit
1
ON
2 3 4 5 6
Capacity setting display
Displayed as an outdoor capacity code.
Code
display
1
ON
2 3 4 5 6
Outdoor unit setting information
(Example) When heat pump, 3 phase and defrosting (nor-
mal) are set up, “20” is displayed.
Code
display
Capacity
Code
FRP71
14
• The tens digit (Total display for applied setting)
Setting details
Display details
H·P/Cooling only 0: H·P
1: Cooling only
Single phase/3 phase 0: Single phase 2: 3 phase
• The ones digit
Setting details
Display details
Defrosting switch
0: Normal
1: For high humidity