OCH665B
2-3. PRECAUTIONS WHEN REUSING EXISTING R22 REFRIGERANT PIPES
(1) Flowchart
Perform the airtight test, vacuum air purging,
additional refrigerant charging (if necessary),
and gas leak check.
• Refer to the flowchart below to determine if the existing pipes can be used and if it is necessary to use a filter dryer.
• If the diameter of the existing pipes is different from the specified diameter, refer to technical data materials to confirm if the
pipes can be used.
▼
▼
▼
▼
▼
▼
▼
Measure the existing pipe thickness and
check for damage.
The existing pipe thickness meets specifica
-
tions and the pipes are not damaged.
Check if the existing air conditioner can operate.
After operating the cooling system for about 30
minutes, do a pump down work.
Disconnect the existing air conditioner from the
pipes.
Attach the new air conditioner
Test run
The existing pipes cannot be reused.
Use new pipes.
• If the existing air conditioner cannot operate, use a
refrigerant recovery device to collect the refrigerant.
• If the existing pipes have been used for gas or oil
heat pump system, use new pipes.
The existing pipe thickness does not meet
specifications or the pipes are damaged.