59
Check of outdoor fan motor
• Fan motor does not operate or stops operating shortly after starting the operation.
Disconnect CN932 and measure the
resistance of the outdoor fan motor.
Turn ON the breaker.
Rotate the outdoor fan motor manually and
measure the voltage of CN931.
Between (+) and (-)
Between (+) and (-)
Between (+) and (-)
Is the resistance of outdoor fan motor
normal? (Refer to 12-5.)
Does the outdoor fan motor rotate smoothly?
Does the voltage between each terminal
become 5 V DC and 0 V DC repeatedly?
Replace the outdoor fan motor.
Replace the inverter P.C. board or the outdoor
control P.C. board.
No
Yes
Yes
No
Yes
No
Connector
MXZ-2HA
CN931
CN932
Inverter P.C. board
MXZ-2HA40VF/2HA50VF
OBH828A