12-5. TROUBLE CRITERION OF MAIN PARTS
Part name
Check method and criterion
Defrost thermistor (RT61)
Fin temperature thermistor (RT64)
Ambient temperature thermistor (RT65)
Outdoor heat exchanger
temperature thermistor (RT68)
Measure the resistance with a tester.
Refer to 12-7. "TEST POINT DIAGRAM AND VOLTAGE" 1. "Inverter P.C. board", 2.
"Outdoor control P.C. board " or 3. "Outdoor power P.C. board" for the chart of thermis-
tor.
Discharge temperature thermistor
(RT62)
Measure the resistance with a tester.
Before measurement, hold the thermistor with your hands to warm it up.
Refer to 12-7. "TEST POINT DIAGRAM AND VOLTAGE" 1. "Inverter P.C. board", 2.
"Outdoor control P.C. board ", for the chart of thermistor.
Compressor
W
U
V
WHT
RED
BLK
Measure the resistance between terminals with a tester.
(Winding temperature : -10°C - 40°C)
Normal (Each phase)
0.86 - 1.06
Outdoor fan motor
2
3
W
U
V
1
WHT
RED BLK
MXZ-2HA40VF/2HA50VF
Measure the resistance between lead wires with a tester.
(Part temperature : -10°C - 40°C)
Normal (Each phase)
32 - 43
Outdoor fan motor
MXZ-3HA50VF
Refer to 12-6. .
R.V. coil
Measure the resistance with a tester. (Part temperature : -10°C - 40°C)
Normal
MXZ-2HA40VF
MXZ-2HA50VF
MXZ-3HA50VF
1.2 k - 1.56 k
1.26 k - 1.62 k
Linear expansion valve
LEV
WHT
RED
YLW
ORN
BLU
Measure the resistance with a tester. (Part temperature : -10°C - 40°C)
Color of lead wire
Normal
WHT - RED
37.4 - 53.9
RED - ORN
YLW - RED
RED - BLU
High pressure switch (HPS)
MXZ-3HA50VF
Pressure
Normal
HPS
3.43 ± 0.15 MPa
Close
4.14 ± 0.1 MPa
Open
MXZ-2HA40VF MXZ-2HA50VF MXZ-3HA50VF
OBH828A