47
-
-
9 times
Lit
Inverter check mode
Lit
Lit
Normal
The connector of compressor is disconnected.
Inverter check mode starts.
-
5 times
Lit
Cooling high pressure
protection
This symptom does not mean any abnormality of the
product, but check the following points.
• Check if indoor filters are clogged.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation is short cycled.
The outdoor heat exchanger temperature exceeds 58°C during operation.
20
LED1(Red) LED2(Yellow)
Abnormal point / Condition
Remedy
Indication
Condition
No. Symptom
Outdoor unit
operates
normally.
22
23
Outdoor unit
operates.
Outdoor display P.C. board (Parts side)
Lit
8 times
Lit
Converter protection
A failure is detected in the operation of the converter during operation.
21
• Check the voltage of power supply.
• Replace the inverter P.C. board.
LED1 LED2
ON
OFF
2.5-second OFF
2.5-second OFF
0.5-second ON
0.5-second ON
NOTE:
1. The location of LED is illustrated at the right figure. Refer to 12-7.4.
2. LED is lighted during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) The blinking frequency is “2”.
OBH828A