54
Check of R.V. coil
The cooling operation or heating operation does not operate.
No
Yes
Yes
Yes
No
No
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in HEAT mode.
Is there voltage of 220 - 230 - 240 V AC between
pin1 and pin2 at connector CN721?
Turn OFF the power supply. Disconnect the connector CN721.
Replace the inverter P.C. board.
Replace the 4-way valve.
Replace the R.V. coil.
Is there normal resistance
to R.V. coil?
(Refer to 12-5.)
1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in COOL mode.
Is there voltage of 220 - 230 - 240 V AC between
pin1 and pin2 at connector CN721?
Replace the inverter P.C. board.
Replace the 4-way valve.
• The heating operation does not operate.
• The cooling operation does not operate.
MXZ-2HA40VF/2HA50VF
Connector
MXZ-2HA
CN721
Inverter P.C. board
OBH828A