40
<MXZ-3HA50VF>
Outdoor unit has an auto line correcting function which automatically detects and corrects improper wiring or piping.
Improper wiring or piping can be automatically detected by pressing the piping/wiring correction switch (SW871).
When improper wiring or piping is detected, wiring lines are corrected.
This will be completed in about 10 to 15 minutes.
[How to activate this function]
1. Check that outside temperature is above 0˚C.
(This function does not work when the outside temperature is 0˚C or below.)
2. Check that the stop valves of the liquid pipe and gas pipe are open.
3. Check that the wiring between indoor and outdoor unit is correct.
(If the wiring is not correct, this function does not work.)
4. Turn ON the power supply and wait at least 1 minute.
5. Press the piping/wiring correction switch (SW871) on the outdoor control P.C. board.
Do not touch energized parts.
6. Press the switch to cancel.
NOTE:
Indoor unit cannot be operated while this function is activated.
When this function is activated while indoor unit is operating, the operation will be stopped.
Operate indoor unit after the auto line correcting is finished.
Pressing the switch during detection cancels this function.
Make sure that the valves are open and the pipes are not collapsed or clogged.
LED indication after cancel :
LED1 (Red)
Lit
LED indication during detection:
LED indication after detection:
LED2 (Yellow)
Lit
LED3 (Green)
Once
LED1 (Red)
Lit
LED2 (Yellow)
Lit
LED3 (Green)
Not lit
LED1 (Red)
Lit
Once
LED2 (Yellow)
Not lit
Once
Other indications
LED3 (Green)
Lit
Once
Completed (Problem corrected/ normal)
Not completed (Detection failed)
Refer to "SAFETY PRECAUTIONS WHEN LED BLINKS"
located behind the top panel.
Result
Press the switch for more than 5 seconds.
LED will show the record of auto correcting for about 30 seconds as shown in the table below:
NOTE:
Activate this function to confirm the correct wiring after replacing the outdoor control P.C. board.
(Previous records are deleted when the outdoor control P.C. board is replaced.)
The record cannot be shown if auto line correcting is not canceled (Refer to "How to activate this function").
LED1 (Red)
Once
3 times
LED2 (Yellow)
Once
3 times
LED3 (Green)
Lit
Lit
Not corrected
Corrected
Number of blinks
Wiring line
The record of auto line correcting can be confirmed in the following way: