16
Outdoor model
MXZ-3HA50VF
Outdoor unit power supply
Single phase
220 - 230 - 240 V, 50 Hz
System
Indoor units number
2 to 3
Piping total length
m
Max. 50
Connecting pipe length
m
Max. 25
Height difference (Indoor ~ Outdoor)
m
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Height difference (Indoor ~ Indoor)
m
Refer to 8 REFRIGERANT SYSTEM DIAGRAM.
Function
Cooling
Heating
Capacity Rated (Min.-Max.) *2
kW
5.0 (2.9 - 6.5)
6.0 (2.6 - 7.5)
Breaker capacity
A
25
Electrical
data
Power input (Total) *1, *2
W
1,260
1,300
Running current (Total) *1, *2
A
5.9 - 5.6 - 5.4 (220V - 230V - 240V) 6.1 - 5.8 - 5.6 (220V - 230V - 240V)
Power factor (Total) *1, *2
%
97
Starting current (Total) *1, *2
A
6.7
Coefficient of performance (C.O.P) (Total)
*1, *2
3.97
4.62
Compressor
Model
SVB130FBBM1T
Output
W
1,300
Current *1, *2
A
5.30
Refrigeration oil (Model)
L
0.6 (FW68S)
Fan
motor
Model
SIC-82FX-F764-1
Current *1, *2
A
0.5
Dimensions W x H x D
mm
840 x 710 x 330
Weight
kg
57
Special
remarks
Air flow (Rated)
m
3
/h
1,860
1,746
Sound level (Rated)
dB(A)
46
50
Fan speed (Rated)
rpm
600
580
Pre-charged refrigerant quantity (R32)
kg
1.4
Max refrigerant quantity (R32)
kg
1.6
*1 Measured under rated operating frequency.
*2 When connected with indoor units below.
MSZ- MSZ- MSZ-HR25VF
NOTE:
Test conditions are based on ISO 5151. (Refrigerant piping length (one way): 5 m)
COOLING INDOOR
Dry-bulb temperature 27.0 °C Wet-bulb temperature 19.0 °C
OUTDOOR Dry-bulb temperature 35.0 °C Wet-bulb temperature 24.0 °C
HEATING INDOOR
Dry-bulb temperature 20.0 °C
OUTDOOR Dry-bulb temperature 7.0 °C Wet-bulb temperature 6.0 °C
OBH828A