background image

14

8.2. Test run

8.2.1.  Using remote controller 

Refer to the indoor unit installation manual.

•  Be sure to perform the test run for each indoor unit. Make sure each indoor unit 

operates properly following the installation manual attached to the unit.

•  If you perform the test run for all indoor units at once, you cannot detect any 

erroneous connection, if any, of the refrigerant pipes and the connecting wires.

*  The compressor operation is not available for 3 minutes at least after the power 

is supplied.

•  The compressor can emit noise just after turn on the power supply or in case of 

low outside air temperature.

About the restart protective mechanism

Once the compressor stops, the restart preventive device operates so the compressor 
will not operate for 3 minutes to protect the air conditioner.

8.2.2.  Using SW4 in outdoor unit

In case of the test run from outdoor unit, all indoor units operate. Therefore, 
you can not detect any erroneous connection of refrigerant pipes and the 
connecting wires. If it aims at detection of any erroneous connection, be 
sure to carry out the test run from remote controller with reference to “8.2.1. 
Using remote controller.”

SW4-1

ON

Cooling operation

SW4-2

OFF

SW4-1

ON

Heating operation

SW4-2

ON

*  After performing the test run, set SW4-1 to OFF.
•  A few seconds after the compressor starts, a clanging noise may be heard from 

the inside of the outdoor unit. The noise is coming from the check valve due to the 
small difference in pressure in the pipes. The unit is not faulty.

The test run operation mode cannot be changed by DIP switch SW4-2 during 
the test run. (To change the test run operation mode during the test run, stop 
the test run by DIP switch SW4-1. After changing the test run operation mode, 
resume the test run by switch SW4-1.)

When a test run is started by “Using SW4 in outdoor unit”, even if it carries 
out stop instructions by remote controller, outdoor unit does not stop (a test 
run is not ended). In this case, please set SW4 in outdoor unit to off.

Note:
Be sure to wait at least 3 minutes after turning on the power supply before set-
ting SW4-1 and SW4-2. If the DIP switches are set before 3 minutes has elapsed, 
the test run may not start.

8. Test run

8.1.  Before test run

 After completing installation and the wiring and piping of the indoor and 

outdoor units, check for refrigerant leakage, looseness in the power supply 
or control wiring, wrong polarity, and no disconnection of one phase in the 
supply.

  Use a 500-volt M-ohm tester to check that the resistance between the power 

supply terminals and ground is at least 1 M

Ω

.

  Do not carry out this test on the control wiring (low voltage circuit) termi-

nals.

 Warning:

Do not use the air conditioner if the insulation resistance is less than 1 M

Ω

.

Insulation resistance

After installation or after the power source to the unit has been cut for an extended 
period, the insulation resistance will drop below 1 M

Ω

 due to refrigerant accumulating 

in the compressor. This is not a malfunction. Perform the following procedures.
1.  Remove the wires from the compressor and measure the insulation resistance of 

the compressor.

2.  If the insulation resistance is below 1 M

Ω

, the compressor is faulty or the resist-

ance dropped due the accumulation of refrigerant in the compressor.

3.  After connecting the wires to the compressor, the compressor will start to warm 

up after power is supplied. After supplying power for the times indicated below, 
measure the insulation resistance again.

 

•  The insulation resistance drops due to accumulation of refrigerant in the com-

pressor. The resistance will rise above 1 M

Ω

 after the compressor is warmed 

up for two to three hours.

 

 

(The time necessary to warm up the compressor varies according to atmospheric 
conditions and refrigerant accumulation.)

 

•  To operate the compressor with refrigerant accumulated in the compressor, the 

compressor must be warmed up at least 12 hours to prevent breakdown.

4.  If the insulation resistance rises above 1 M

Ω

, the compressor is not faulty.

 Caution:

  The compressor will not operate unless the power supply phase connection 

is correct.

•  Turn on the power at least 12 hours before starting operation.

-  Starting operation immediately after turning on the main power switch can result 

in severe damage to internal parts. Keep the power switch turned on during the 
operational season.

  The followings must be checked as well.

•  The outdoor unit is not faulty. LED on the control board of the outdoor unit flash 

when the outdoor unit is faulty.

•  Both the gas and liquid stop valves are completely open.

Summary of Contents for MXZ-160VA-A

Page 1: ...TALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners OUTDOOR UNIT MXZ 8B140 160VA A FOR INSTALLER HFC utilized R410A ...

Page 2: ...ock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazar...

Page 3: ...s that carried R22 refriger ant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 6 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdown may ...

Page 4: ...serving the table below The unit s quantities are limited in 2 to 8 units For the next step make sure that the total rated capacity selected will stay in a range as shown below MXZ 8B140 3 0 18 5kw MXZ 8B160 3 0 20 2kw Example MXZ 8B140 MSZ 60 6 0 SEZ 35 3 5 SLZ 35 3 5 SEZ 25 2 5 SLZ 25 2 5 Indoor unit type 15 20 22 25 35 42 50 60 71 80 100 1 Rated capacity Cooling kW 1 5 2 0 2 2 2 5 3 5 4 2 5 0 6...

Page 5: ... more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow Obstacles at front only Fig 3 13 When using an optional air outlet guide the clearance is 1000 mm or more Obstacles at front and rear only Fig 3 14 When using an optional air outlet guide the clearance is 1000 mm or more Single parallel unit arrange...

Page 6: ...ervicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified ...

Page 7: ... of using 1 branch box Flare connection employed No brazing N In case of using 2 branch boxes Branch box 1 2 branches pipe joint optional parts Branch box 2 Conversion formula 1 4 F ø6 35 3 8 F ø9 52 1 2 F ø12 7 5 8 F ø15 88 3 4 F ø19 05 5 3 Addition of refrigerant Additional charging is not necessary for this unit if the total pipe length b1 b2 a1 a2 a3 a4 a5 a6 a7 a8 does not exceed 40 m If the ...

Page 8: ...ry If it is used a gas leakage or even a pipe extraction may occur 2 For details about connecting the pipes for the P100 indoor unit refer to the installation manual of the Y shape connection pipe PAC AK52YP E When bending the pipes be careful not to break them Bend radii of 100 mm to 150 mm are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result Pipe...

Page 9: ... in Cap Wrench hole Completely closed Operation section LO HI A C D B K E F G H I Fig 5 11 5 8 Airtight test and evacuation Airtight test Fig 5 11 Airtight test should be made by pressurizing nitrogen gas For the test method refer to the following figure 1 Connecting the testing tool Make a test with the stop valve closed Be also sure to pressurize both liquid or high pressure pipe and gas or low p...

Page 10: ... pipe and gas or low pressure pipe with the stop valve closed Remember Never carry out air purge by refrigerant Warning When installing or moving a unit to another place do not mix anything other than specified refrigerant into the refrigeration cycle If air is mixed the refrigeration cycle may obtain abnormally high pressure resulting in a burst pipe A high precision gravimeter measurable up to 0 ...

Page 11: ...not be operated by a single remote controller 3 2 Different refrigerant systems cannot be connected together 3 3 A M NET adapter cannot be connected to an outdoor unit 3 1 Group operation by single remote controller 3 2 Group operation between different refrigerant systems 3 3 Connection of M NET adapter to outdoor unit Master controller G 50 etc Power supply unit 2 1 Only 3 branch type 2 2 Only 5...

Page 12: ...ower supply work can be carried out at just one spot of the outdoor unit It will contribute to simplify the work and save costs Power supply Model Power supply 140 160V N 220 230 240V 50Hz N 220V 60Hz Max Permissive System Impedance 0 22 Ω Note Power supply input Outdoor unit only Connect the lines C D in accordance with the terminal block names to ensure correct polarity Model Wire diameter Break...

Page 13: ...ermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the inter mediate connection point If an intermediate connection is necessary be sure to take measures to prevent water from entering the cables 1 Power supply cords of appliances shall not be lighter than design 60245 IEC or 227 IEC 2 In cas...

Page 14: ...t run may not start 8 Test run 8 1 Before test run After completing installation and the wiring and piping of the indoor and outdoor units check for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply Use a 500 volt M ohm tester to check that the resistance between the power supply terminals and ground is at least 1 MΩ ...

Page 15: ...ration mode locking func tion by external signal CN3S Remote control panel Relay circuit External input adapter PAC SC36NA Outdoor unit control board Relay power supply Procure locally Max 10m ON OFF SW1 Heating Cooling SW2 Validity of SW1 Invalidity of SW1 Any indoor unit that is operating in a mode different from the one specified by the external signal will enter the standby mode The setting bec...

Page 16: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U438L01 ...

Reviews: