background image

9

5.  Installing the refrigerant piping

5.7.  Caution for piping connection/valve operation

•  Conduct piping connection and valve operation accurately by following the figure 

below.

•  Apply sealer along the insulator to prevent water entering the insulator covering the 

refrigerant pipe joints.

•  After evacuation and refrigerant charge, ensure that the handle is fully open. If 

operating with the valve closed, abnormal pressure will be imparted to the high- or 
low-pressure side of the refrigerant circuit, giving damage to the compressor, etc. 

•  Determine the amount of additional refrigerant charge (refer “5.3. Addition of refriger-

ant”), and charge refrigerant additionally through the service port after completing 
piping connection work.

•  After completing work, tighten the service port (12 - 15 N·m) and cap (20 - 25 N·m) 

securely to prevent gas leak.

*1 N·m

   

10 kgf·cm

Method of completely opening the stop valve

The stop valve opening method varies according to the outdoor unit model. Use the 
appropriate method to open the stop valves.
(1) Type A (Fig. 5-9)

  Remove the cap, then turn one-quarter rotation counter-clockwise with a flat-bladed 

screwdriver to complete open.

  Check that the valves are fully open, then return the cap to its original state and 

tighten it down.

(2) Type B (Fig. 5-9)

  Remove the cap, pull the handle toward you and rotate 1/4 turn in a counterclock-

wise direction to open.

  Make sure that the stop valve is open completely, push in the handle and rotate 

the cap back to its original position.

(3) Type C (Fig. 5-10)

  Remove the cap and turn the valve rod counterclockwise as far as it will go with 

the use of a 4 mm hexagonal wrench. Stop turning when it hits the stopper.

  Make sure that the stop valve is open completely and rotate the cap back to its 

original position.

Valve

Completely open

Unit side

(On-side installation) Refrigerant 
piping side

Service port

Handle

Direction the refrigerant flows in

Cap

Wrench hole

Completely closed

Operation section

LO

HI

A

C

D

B

K

E

F

G

H
I

Fig. 5-11

5.8.  Airtight test and evacuation

 

Airtight test (Fig. 5-11)

Airtight test should be made by pressurizing nitrogen gas. For the test method, refer 
to the following figure.
(1) Connecting the testing tool. Make a test with the stop valve closed. Be also sure 

to pressurize both liquid or high-pressure pipe and gas or low pressure pipe. 

(2) Do not add pressure to the specified pressure all at once; add pressure little by lit-

tle.

 Pressurize to 0.5 MPa (5 kgf/cm

2

G), wait five minutes, and make sure the  

pressure does not decrease.

 Pressurize to 1.5 MPa (15 kgf/cm

2

G), wait five minutes, and make sure the 

pressure does not decrease.

 Pressurize to 4.15 MPa (41.5 kgf/cm

2

G) and measure the surrounding tem-

perature and refrigerant pressure.

(3) If the specified pressure holds for about one day and does not decrease, the pipes 

have passed the test and there are no leaks.

•  If the surrounding temperature changes by 1 °C, the pressure will change by 

about 0.01 MPa (0.1 kgf/cm

2

G). Make the necessary corrections.

(4) If the pressure decreases in steps (2) or (3), there is a gas leak. Look for the source 

of the gas leak.

Nitrogen gas

Stop valve

System analyzer

Liquid pipe or high-pressure 
pipe

Lo-knob

Hi-knob

Gas pipe or low-pressure pipe

To branch box

Service port

Outdoor unit

Fig. 5-9

Fig. 5-10

Type A

Type B

F

H

C

A

B

D

E

G

B

C

J

I

H

E

(1)

(2)

(3)

Type C

A

B

K

E

H

C

5.6.  Refrigerant piping (Fig. 5-8)

Remove the service panel 

 (three screws) and the front piping cover 

 (two screws) 

and rear piping cover 

 (two screws).

Refrigerant pipes are protectively wrapped
•  The pipes can be protectively wrapped up to a diameter of ø90 before or after con-

necting the pipes. Cut out the knockout in the pipe cover following the groove and 
wrap the pipes.

Pipe inlet gap
•  Use putty or sealant to seal the pipe inlet around the pipes so that no gaps re-

main.

  (If the gaps are not closed, noise may be emitted or water and dust will enter the 

unit and breakdown may result.)

Fig. 5-8

  Front piping cover

 Piping cover

 Stop valve

Service panel

  Band radius : 100 mm - 150 mm

Summary of Contents for MXZ-160VA-A

Page 1: ...TALLATION MANUAL For safe and correct use please read this installation manual thoroughly before installing the air conditioner unit Air Conditioners OUTDOOR UNIT MXZ 8B140 160VA A FOR INSTALLER HFC utilized R410A ...

Page 2: ...ock or fire may result When installing or relocating or servicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pressure in the refrigerant line and may result in an explosion and other hazar...

Page 3: ...s that carried R22 refriger ant Replace the existing flare nuts and flare the flared sections again Do not use thin pipes Refer to page 6 Store the pipes to be used during installation indoors and keep both ends of the pipes sealed until just before brazing Leave elbow joints etc in their packaging If dust debris or moisture enters the refrigerant lines oil dete rioration or compressor breakdown may ...

Page 4: ...serving the table below The unit s quantities are limited in 2 to 8 units For the next step make sure that the total rated capacity selected will stay in a range as shown below MXZ 8B140 3 0 18 5kw MXZ 8B160 3 0 20 2kw Example MXZ 8B140 MSZ 60 6 0 SEZ 35 3 5 SLZ 35 3 5 SEZ 25 2 5 SLZ 25 2 5 Indoor unit type 15 20 22 25 35 42 50 60 71 80 100 1 Rated capacity Cooling kW 1 5 2 0 2 2 2 5 3 5 4 2 5 0 6...

Page 5: ... more than three units must be installed side by side In addition leave space as shown Do not install the optional air outlet guides for upward airflow Obstacles at front only Fig 3 13 When using an optional air outlet guide the clearance is 1000 mm or more Obstacles at front and rear only Fig 3 14 When using an optional air outlet guide the clearance is 1000 mm or more Single parallel unit arrange...

Page 6: ...ervicing the air conditioner use only the specified refrigerant R410A to charge the refrigerant lines Do not mix it with any other refrigerant and do not allow air to remain in the lines If air is mixed with the refrigerant then it can be the cause of abnormal high pres sure in the refrigerant line and may result in an explosion and other hazards The use of any refrigerant other than that specified ...

Page 7: ... of using 1 branch box Flare connection employed No brazing N In case of using 2 branch boxes Branch box 1 2 branches pipe joint optional parts Branch box 2 Conversion formula 1 4 F ø6 35 3 8 F ø9 52 1 2 F ø12 7 5 8 F ø15 88 3 4 F ø19 05 5 3 Addition of refrigerant Additional charging is not necessary for this unit if the total pipe length b1 b2 a1 a2 a3 a4 a5 a6 a7 a8 does not exceed 40 m If the ...

Page 8: ...ry If it is used a gas leakage or even a pipe extraction may occur 2 For details about connecting the pipes for the P100 indoor unit refer to the installation manual of the Y shape connection pipe PAC AK52YP E When bending the pipes be careful not to break them Bend radii of 100 mm to 150 mm are sufficient Make sure the pipes do not contact the compressor Abnormal noise or vibration may result Pipe...

Page 9: ... in Cap Wrench hole Completely closed Operation section LO HI A C D B K E F G H I Fig 5 11 5 8 Airtight test and evacuation Airtight test Fig 5 11 Airtight test should be made by pressurizing nitrogen gas For the test method refer to the following figure 1 Connecting the testing tool Make a test with the stop valve closed Be also sure to pressurize both liquid or high pressure pipe and gas or low p...

Page 10: ... pipe and gas or low pressure pipe with the stop valve closed Remember Never carry out air purge by refrigerant Warning When installing or moving a unit to another place do not mix anything other than specified refrigerant into the refrigeration cycle If air is mixed the refrigeration cycle may obtain abnormally high pressure resulting in a burst pipe A high precision gravimeter measurable up to 0 ...

Page 11: ...not be operated by a single remote controller 3 2 Different refrigerant systems cannot be connected together 3 3 A M NET adapter cannot be connected to an outdoor unit 3 1 Group operation by single remote controller 3 2 Group operation between different refrigerant systems 3 3 Connection of M NET adapter to outdoor unit Master controller G 50 etc Power supply unit 2 1 Only 3 branch type 2 2 Only 5...

Page 12: ...ower supply work can be carried out at just one spot of the outdoor unit It will contribute to simplify the work and save costs Power supply Model Power supply 140 160V N 220 230 240V 50Hz N 220V 60Hz Max Permissive System Impedance 0 22 Ω Note Power supply input Outdoor unit only Connect the lines C D in accordance with the terminal block names to ensure correct polarity Model Wire diameter Break...

Page 13: ...ermediate connections can lead to communication errors if water enters the cables and causes insufficient insulation to ground or a poor electrical contact at the inter mediate connection point If an intermediate connection is necessary be sure to take measures to prevent water from entering the cables 1 Power supply cords of appliances shall not be lighter than design 60245 IEC or 227 IEC 2 In cas...

Page 14: ...t run may not start 8 Test run 8 1 Before test run After completing installation and the wiring and piping of the indoor and outdoor units check for refrigerant leakage looseness in the power supply or control wiring wrong polarity and no disconnection of one phase in the supply Use a 500 volt M ohm tester to check that the resistance between the power supply terminals and ground is at least 1 MΩ ...

Page 15: ...ration mode locking func tion by external signal CN3S Remote control panel Relay circuit External input adapter PAC SC36NA Outdoor unit control board Relay power supply Procure locally Max 10m ON OFF SW1 Heating Cooling SW2 Validity of SW1 Invalidity of SW1 Any indoor unit that is operating in a mode different from the one specified by the external signal will enter the standby mode The setting bec...

Page 16: ...ase be sure to put the contact address telephone number on this manual before handing it to the customer HEAD OFFICE TOKYO BLDG 2 7 3 MARUNOUCHI CHIYODA KU TOKYO 100 8310 JAPAN Printed in Japan BG79U438L01 ...

Reviews: