6
Model name
Indoor unit
PLA-RP71AA
PLA-RP100AA2
PLA-RP125AA2 PLA-RP140AA2
Outdoor unit
PU-P71VHA
PU-P71YHA
PU-P100VHA
PU-P100YHA
PU-P125YHA
PU-P140YHA
Cooling
Capacity
Btu/h
27,300
34,100
42,000
48,500
kW
8.0
10.0
12.3
14.2
Total input
kW
2.83
3.53
4.36
5.41
EER
2.83
2.83
2.82
2.62
Energy label class
C
C
C
D
SHF
0.74
0.78
0.74
0.71
Heating
Capacity
Btu/h
-
-
-
-
kW
-
-
-
-
Total input
kW
-
-
-
-
COP
-
-
-
-
Energy label class
-
-
-
-
Booster heater
kW
-
-
-
-
Power supply
Phase
[
1
3
1
3
3
Cycle
Hz
50
50
50
50
50
Voltage
V
230
400
230
400
400
Breaker size
A
32
16
32
16
25
Indoor unit
Air flow
CMM
15-16-18-20
19-21-23-27
24-25-27-30
(Low-Medium2-Medium1-High)
CFM
530-565-635-705
670-740-810-950
850-880-950-1060
External pressure
Pa
0
0
0
Sound level
dB(A)
28-30-32-34
33-36-39-41
37-40-43-45
(Low-Medium2-Medium1-High)
External finish (Panel)
White Munsell 0.70Y 8.59/0.97
Dimension
W : mm
840 (950)
840 (950)
Unit (Panel)
D : mm
840 (950)
840 (950)
H : mm
258 (30)
298 (30)
W : inch
33-1/16 (37-3/8)
33-1/16 (37-3/8)
D : inch
33-1/16 (37-3/8)
33-1/16 (37-3/8)
H : inch
10-3/16 (1-3/16)
11-3/4 (1-3/16)
Weight
kg
24 (5)
32 (5)
Unit (Panel)
lbs
53 (11)
71 (11)
Unit drain pipe I.D.
mm
32
32
inch
1-1/4
1-1/4
Outdoor unit
Air flow
CMM
55
65
100
CFM
1,940
2,290
3,530
Sound level at cooling
dB(A)
49
50
50
51
Sound level at heating
dB(A)
–
–
–
–
External finish
Ivory Munsell 5Y 7/1
Dimension
W : mm
950
950
950
D : mm
330+30
330+30
330+30
H : mm
943
943
1350
W : inch
37-3/8
37-3/8
37-3/8
D : inch
13 + 1-3/16
13 + 1-3/16
13 + 1-3/16
H : inch
37-1/8
37-1/8
53-1/8
Weight
kg
93
94
131
lbs
205
207
289
Refrigerant pipe size
Gas side O.D.
mm
15.88
15.88
15.88
inch
5/8
5/8
5/8
Liquid side O.D.
mm
9.52
9.52
9.52
inch
3/8
3/8
3/8
Refrigerant pipe length Height difference
m
Max. 50
Max. 50
Max. 50
Length
m
Max. 50
Max. 50
Max. 50
NOTE:
1. Rating conditions (ISO T1)
Cooling Indoor : D.B. 27
:
(80˚F) W.B. 19
:
(66˚F)
Outdoor : D.B. 35
:
(95˚F) W.B. 24
:
(75˚F)
Refrigerant piping length (one way) : 5m (16ft.)
2. Guaranteed operating range
Indoor
Outdoor
Cooling
Upper limit D.B. 35˚C, W.B. 22.5˚C D.B. 46
:
Lower limit D.B. 19˚C, W.B. 15˚C
D.B. -5
:
w
4. Above data are based on the indicated voltage
w
If optional Air protect guide installed. D.B.-15
:
Indoor unit
Single phase 230V 50Hz
Single phase 230V 50Hz
/ 3 phase 400V 50Hz
Outdoor unit
3. Guaranteed voltage
198~264V, 50Hz : Single phase
342~457V, 50Hz : 3 phase
OCS07B-1.qxp 07.4.10 0:44 PM Page 6
Summary of Contents for Mr.SLIM PKA-RP FAL2
Page 37: ...37 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Page 38: ...38 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Page 66: ...66 9 3 PLA RP AA PLA RP AA2 9 3 1 FRESH AIR INTAKE AMOUNT ...
Page 67: ...67 9 3 2 BRANCH DUCT Installation at site ...
Page 77: ...77 PEAD RP60GA PEAD RP71GA ...
Page 78: ...78 PEAD RP100GA ...
Page 85: ...85 ...