56
7
CORRECTION FACTORS
Refrigerant piping length (one way)
55m
50m
40m
30m
20m
10m
5m
Outdoor unit
7-1. COOLING CAPACITY CORRECTION FACTORS
PU(H)-P71VHA
PU(H)-P71YHA
PU(H)-P100VHA
PU(H)-P100YHA
PU(H)-P125YHA
PU(H)-P140YHA
PUH-P71VHA
PUH-P71YHA
PUH-P100VHA
PUH-P100YHA
PUH-P125YHA
PUH-P140YHA
Outdoor unit
Refrigerant piping length (one way)
55m
50m
40m
30m
20m
10m
5m
7-2. HEATING CAPACITY CORRECTION FACTORS
1.00
1.00
1.00
1.00
0.988
0.985
0.981
0.976
0.966
0.957
0.946
0.931
0.946
0.931
0.914
0.893
0.929
0.908
0.885
0.858
0.913
0.886
0.858
0.827
0.905
0.876
0.845
0.813
1.00
1.00
1.00
1.00
0.997
0.997
0.997
0.997
0.991
0.991
0.991
0.991
0.985
0.985
0.985
0.985
0.979
0.979
0.979
0.979
0.973
0.973
0.973
0.973
0.970
0.970
0.970
0.970
OCS07B-2.qxp 07.4.10 0:41 PM Page 56
Summary of Contents for Mr.SLIM PKA-RP FAL2
Page 37: ...37 WIRED REMOTE CONTROLLER Unit mm 130 120 19 ...
Page 38: ...38 WIRELESS REMOTE CONTROLLER Unit mm 159 3 55 58 19 ...
Page 66: ...66 9 3 PLA RP AA PLA RP AA2 9 3 1 FRESH AIR INTAKE AMOUNT ...
Page 67: ...67 9 3 2 BRANCH DUCT Installation at site ...
Page 77: ...77 PEAD RP60GA PEAD RP71GA ...
Page 78: ...78 PEAD RP100GA ...
Page 85: ...85 ...