11
(OHFWULFDOZRUN
7. Test run
7.1. Before test run
Ź$IWHUFRPSOHWLQJLQVWDOODWLRQDQGWKHZLULQJDQGSLSLQJRIWKHLQGRRUDQG
outdoor units, check for refrigerant leakage, looseness in the power sup-
ply or control wiring, wrong polarity, and no disconnection of one phase
in the supply.
Ź 8VH D YROW PHJRKPPHWHU WR FKHFN WKDW WKH UHVLVWDQFH EHWZHHQ WKH
SRZHUVXSSO\WHUPLQDOVDQGJURXQGLVDWOHDVW0
.
Ź'RQRWFDUU\RXWWKLVWHVWRQWKHFRQWUROZLULQJORZYROWDJHFLUFXLWWHUPL
-
nals.
Warning:
'RQRWXVHWKHDLUFRQGLWLRQHULIWKHLQVXODWLRQUHVLVWDQFHLVOHVVWKDQ0
.
7.2. Test run
The following 3 methods are available.
7.2.1. Using wired remote controller (Fig. 7-1)
Turn on the power at least 12 hours before the test run.
Press the [TEST] button twice.
“TEST RUN” liquid crystal display
Press the [Mode selection] button and switch to the cooling (or heating) mode.
Make sure that cold (or warm) wind is blown out.
Press the [Fan speed] button.
Make sure that the wind speed is switched.
Press the [Air direction button] or [Louver button].
Check operation of the vane or louver.
Check operation of the outdoor unit fan.
Release test run by pressing the [ON/OFF] button.
Stop
Register a telephone number.
7KHWHOHSKRQHQXPEHURIWKHUHSDLUVKRSVDOHVRI¿FHHWFWRFRQWDFWLIDQHUURU
occurs can be registered in the remote controller. The telephone number will be
displayed when an error occurs. For registration procedures, refer to the opera-
tion manual for the indoor unit.
7.2.2. Using wireless remote controller (Fig. 7-2)
Turn on the power to the unit at least 12 hours before the test run.
Press the
TEST RUN
button twice continuously.
(Start this operation from the status of remote controller display turned off.)
TEST RUN
and current operation mode are displayed.
Press the
MODE
button to activate
mode, then check whether
cool air is blown out from the unit.
Press the
MODE
button to activate
mode, then check whether
warm air is blown out from the unit.
Press the
FAN
button and check whether fan speed changes.
Press the
VANE
button and check whether the auto vane operates properly.
Press the ON/OFF button to stop the test run.
Note:
• Point the remote controller towards the indoor unit receiver while following
steps
to
.
• It is not possible to run the TEST RUN in FAN, DRY or AUTO mode.
7.2.3. Using SW4 in outdoor unit
Refer to the outdoor unit installation manual.
ON/OFF
TEMP
FAN
VANE
TEST RUN
AUTO STOP
AUTO START
h
min
LOUVER
MODE
CHECK
RESET
SET
CLOCK
TEST RUN
Fig. 7-2
Fig. 7-1
°C
°C
SIMPLE
PAR-21MAA
ON/OFF
FILTER
CHECK
OPERATION
CLEAR
TEST
TEMP.
MENU
BACK
DAY
MONITOR/SET
CLOCK
ON/OFF
TEST RUN
COOL, HEAT
ON/OFF button
Test run display
Liquid pipe (Indoor unit)
temperature display
ON/OFF lamp
Power display
Error code display
Test run remaining time display
Set temperature button
Mode selection button
Air direction button
TEST button
!
Fan Speed button
"
Louver button
"!
Select unit numbers 01 to 03 or all units (AL [wired remote controller]/07 [wireless remote controller])
Mode
Settings
Mode no.
Setting no. Initial setting
setting
Filter sign
100Hr
07
1
2500Hr
2
ȅ
1R¿OWHUVLJQLQGLFDWRU
3
Fan speed
Silent
08
1
Standard
2
ȅ
High ceiling
3
Up/down vane setting
No vanes
11
1
Equipped with vanes (vanes angle setup
)
2
ȅ
Equipped with vanes (vanes angle setup
)
3
+
When the power supply returns, the air conditioner will start 3 minutes later.