3.13.2 Setting and Monitoring AI Controllers (63MC)
AI Controller (PAC-YG63MCA) is capable of measuring the temperature and humidity.
Trend displays of measurement data can be shown on the G(B)-50A Web Browser and TG-2000A.
Furthermore, an alarm can be output if measurement data exceeds a preset upper or lower limit.
The function allotment of AI Controller, G(B)-50A Web Browser,TG-2000A and Maintenance Tools is as
follows.
[Note] S:Setting possibility, M:Monitoring only, -:None
Function name
AI Controller
G(B)-50A
Web
TG-2000A Maintenance
Tools
Address setting
S
*1
-
- M
Setting of the input to use
S
*1
-
- M
Setting of the analog input
type
S
*1
-
- M
Range and category
setting of sensor
- S
S M
(Operation is possible)*2
Setting of upper/lower limit
alarm interlock output use
S
*1
-
- M
Range setting of
Upper/Lower limit alarm
- S
S M
(Operation is possible)*2
Monitoring and trend
displays of measurement
data
- S
S M
(Monitoring only)
Time setting
-
S
S
M
(Operation is possible)*2
Temperature sensor,
Humidity sensor, etc
Max.
Temperature 1
Humidity 1
(3)(4)
(1)(2)
(1) Channel 1 temperature or humidity sensor input
(2) Channel 2 temperature or humidity sensor input
(3) Channel 1 upper/lower limit alarm output
(4) Channel 2 upper/lower limit alarm output
Hub
G(B)-50A
Outdoor unit
Indoor units
M-NET
M-NET
AI controller
TG-2000A
24 VDC
Power supply
G(B)-50A Web
*1 It is set with Dip switch of AI Controller.
*2 When G(B)-50A or TG-2000A is connected, the setting must be made on G(B)-50A Web Browser or TG-2000A.