63
1. OUTLINE
1.4 Connection and parameter setting
1
2
3
4
5
6
7
8
9
10
*1
The setting is applied after an inverter reset or next power-ON.
*2
The setting is available for the FR-E800-E only.
*3
The setting is available only for the FR-E800-EPB and the FR-E800-SCEPB.
1330 to
1343
N850 to
N863
User Defined Cyclic
Communication Output 1 to 14
Mapping
9999
6
, 12288 to
13787, 16384 to
16483, 20488,
20489, 20981 to
20990, 20992
,
24639, 24643,
24644, 24673 to
24676, 24692,
24695, 24820,
24826, 24828,
25858
Set the index number for inverter parameters, monitor
data, inverter control parameters, and CiA402 drive
profile. Functions can be assigned to remote registers
RWrn+4 to RWrn+1F when
Pr.544
= "38".
9999
Function disabled
User Defined Cyclic
Communication Input Sub 1
and 2 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1389
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1320Pr.1389
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1321
User Defined Cyclic
Communication Input Sub 3
and 4 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1390
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1322Pr.1390
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1323
User Defined Cyclic
Communication Input Sub 5
and 6 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1391
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1324Pr.1391
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1325
User Defined Cyclic
Communication Input Sub 7
and 8 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1392
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1326Pr.1392
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1327
User Defined Cyclic
Communication Input Sub 9
and 10 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1393
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1328Pr.1393
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1329
N830 to
N839
User Defined Cyclic
Communication Input Sub 1 to
10 Mapping
0
0 to 2
Subindices to which the index numbers are specified
using
Pr.1320 to Pr.1329
User Defined Cyclic
Communication Output Sub 1
and 2 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1394
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1330Pr.1394
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1331
User Defined Cyclic
Communication Output Sub 3
and 4 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1395
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1332Pr.1395
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1333
User Defined Cyclic
Communication Output Sub 5
and 6 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1396
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1334Pr.1396
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1335
User Defined Cyclic
Communication Output Sub 7
and 8 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1397
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1336Pr.1397
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1337
User Defined Cyclic
Communication Output Sub 9
and 10 Mapping
0
0 to 2, 256 to 258,
512 to 514
Pr.1398
(lower 8 bits): Subindex to which the index
number is specified using
Pr.1338Pr.1398
(upper 8 bits):
Subindex to which the index number is specified using
Pr.1339
N870 to
N879
User Defined Cyclic
Communication Output Sub 1
to 10 Mapping
0
0 to 2
Subindices to which the index numbers are specified
using
Pr.1330 to Pr.1339
804
D400
Torque command source
selection
0
0, 1, 3 to 6
In the torque control mode, the torque command source
can be selected.
810
H700
Torque limit input method
selection
0
0 to 2
The torque limit input method can be selected.
Pr.
Name
Initial value
Setting range
Description