225
4. TROUBLE INDICATION
4.1 Error code
1
2
3
4
5
6
7
8
9
10
4.1.3
List of errors related to functional safety
NOTE
• If a timeout error occurs, set the FR Configurator2 to the offline mode. Check the connection of the communication cable, etc.,
and remove any error causing condition, then set it to online.
• FR Configurator2 shows the safety parameters of the latest inverter at the time of the FR Configurator2 upgrade. (For the
upgrade timing of FR Configurator2, refer to
.) The parameters' setting range, initial value, and numbers may be
different before and after a version upgrade (with functions added).
0x80112405
An unexpected error occurred in
S/W.
Network error
Check that the GOT is connected to
the network.
0x80112406
An unexpected error occurred in
S/W.
Connected socket forced
disconnection
Check that the GOT is not making a
communication in other connection
method.
Error code (HEX)
Error message
Possible cause
Solution
Error code (HEX)
Error message
Countermeasure
0x01A0000B
Parameters of the inverter used are not
supported by the existing version of FR
Configurator2.
Upgrade FR configurator2 to the latest version.
0x01A00117
Safety parameter settings are corrupt.
• Retry the operation interrupted by the fault.
• Perform safety parameter clear.
If the problem still persists after taking the above measure, contact
your sales representative.
0x01A00217
0x01A00417
0x01A00301
0x01A00303
0xA001**01
An unexpected error occurred in S/W.
Please contact your sales representative.
0xA002**01
0xA001**02
0xA002**02
0xA001**03
0xA002**03
0xA001**04
A communication error occurred.
Check the noise and wiring.
0xA002**04
0xA001**05
An unexpected error occurred in S/W.
Please contact your sales representative.
0xA002**05
0xA001**10
A safety parameter reading error
occurred.
• Retry the operation interrupted by the fault.
• Perform safety parameter clear.
If the problem still persists after taking the above measure, contact
your sales representative.
0xA002**10
0xA001**11
A safety parameter writing error occurred.
0xA002**11
0xA001**12
An unexpected error occurred in S/W.
Please contact your sales representative.
0xA002**12
0xA001**13
0xA002**13
0xA001**14
0xA002**14
0xA001**15
Any value out of the setting range cannot
be written.
Write a value within the setting range.
0xA002**15