3. Terminals
3.1 Terminal blocks
Symbol Signal
Description
Main circuit power input terminals
1) 200V Class
Supply L
1
, L
2
and L
3
with the following power.
For a single-phase 230VAC power supply, connect the power supply to L1 and
L2 and keep L3 open:
Servo amplifier
Power supply
MR-J2-10A to 70A
MR-J2-100A to 700A
3-phase 200 to 230VAC,
50/60Hz
L
1
•L
2
•L
3
Single-phase 230VAC,
50/60Hz
L
1
•L
2
L
1
, L
2
, L
3
Main circuit power supply
Cannot be used for combination with the servo motor HC-SFS52•53.
2) 100V Class
Supply L1, L2 with the single-phase 100 to 120V 50/60Hz power.
U, V, W
Servo motor output
Servo motor power output terminalss
Connect to the servo motor power supply terminals (U, V, W).
L
11
, L
21
Control circuit power supply
Control circuit power input terminals
1) 200V Class
Supply L11 and L21 with single-phase 200-230VAC, 50/60Hz power.
2) 100V Class
Supply L11 and L21 with single-phase 100-120VAC, 50/60Hz power.
P, C, D
Regenerative brake option
Regenerative brake option connection terminals
C and D are factory-connected.
When using the regenerative brake option, always remove wiring from across
P-D and connect the regenerative brake option across P-C.
N
Do not connect.
Protective earth (PE)
Ground terminal
Connect this terminal to the protective earth (PE) terminals of the servo
motor and control box for grounding.