![Mitsubishi Electric MELSERVO-J2S-S061 Specifications And Instruction Manual Download Page 48](http://html.mh-extra.com/html/mitsubishi-electric/melservo-j2s-s061/melservo-j2s-s061_specifications-and-instruction-manual_239181048.webp)
47
8. Communication Functions
The MR-J2S-A-S061 has the RS-422 and RS-232C serial communication functions. These functions can
be used to perform servo operation, parameter changing, monitor function, etc.
However, the RS-422 and RS-232C communication functions cannot be used together. Select between RS-
422 and RS-232C with parameter No.16.
8.1 Configuration
8.1.1 RS-422 configuration
(1) Outline
Up to 32 axes of servo amplifiers from stations 0 to 31 can be operated on the same bus.
CHARGE
MITSUBISHI
CHARGE
MITSUBISHI
CHARGE
MITSUBISHI
RS-422
Controller such as
personal computer
RS-232C/
RS-422
converter
Servo amplifier
Servo amplifier
To
CN3
Axis 1 (Station 0)
Axis 2 (Station 1)
Axis 32 (Station 31)
Unavailable as option.
To be prepared by customer.
Servo amplifier
To
CN3
To
CN3
(2) Cable connection diagram
Wire as shown below:
RDP
RDN
SDP
SDN
GND
GND
5
15
9
19
11
1
10
RDP
RDN
SDP
SDN
LG
LG
TRE
SD
5
15
9
19
11
1
10
RDP
RDN
SDP
SDN
LG
LG
TRE
SD
5
15
9
19
11
1
10
RDP
RDN
SDP
SDN
LG
LG
TRE
SD
(Note 3) 30m(1181.10inch) max.
Plate
(Note 1)
Axis 2 servo amplifier
CN3 connector
Plate
Plate
(Note 2)
RS-422
output unit
(Note 1)
Axis 1 servo amplifier
CN3 connector
(Note 1)
Axis 32 (last axis)
servo amplifier
CN3 connector
Note: 1. 3M's CN3 connector
Connector: 10120-3000VE
Shell kit: 10320-52F0-008
2. In the last axis, connect TRE and RDN.
3. 30m(1181.10inch) max. in environment of little noise.