28
2 SPECIFICATIONS
2.2 Power Supply Specifications
2.2
Power Supply Specifications
The CPU module power supply specifications are explained below.
For the consumption current of extension modules, refer to
Page 39 PRODUCT LIST or manuals of each extension
module.
AC power supply type
*1 This item shows value when all 24 V DC service power supplies are used in the maximum configuration connectable to the CPU
module. (The current of the input circuit is included.)
*2 When I/O modules are connected, they consume current from the 24 V DC service power supply.
For details on the 24 V DC service power supply, refer to
Page 56 Limitation on Current Consumption.
The following shows the power failure detection time of the AC power supply type.
Item
Specifications
Rated voltage
100 to 240 V AC
Voltage fluctuationge range
-15%, +10%
Frequency rating
50/60 Hz
Allowable instantaneous power failure time
Operation can be continued upon occurrence of instantaneous power failure for 10 ms or less.
When the supply voltage is 200 V AC or higher, the time can be change to 10 to 100 ms by editing the user
program.
Power fuse
250 V, 3.15 A Time-lag fuse
Rush current
FX5UJ-24M
25 A max. 5 ms or less/100 V AC
50 A max. 5 ms or less/200 V AC
FX5UJ-40M
,
FX5UJ-60M
30 A max. 5 ms or less/100 V AC
50 A max. 5 ms or less/200 V AC
Power consumption
FX5UJ-24M
30W
FX5UJ-40M
32W
FX5UJ-60M
35W
24 V DC service power
supply capacity
FX5UJ-24M
400 mA (Supply capacity when 24 V DC service power supply is used for input circuit of the CPU module )
460 mA (Supply capacity when external power supply is used for input circuit of the CPU module)
FX5UJ-40M
400 mA (Supply capacity when 24 V DC service power supply is used for input circuit of the CPU module )
500 mA (Supply capacity when external power supply is used for input circuit of the CPU module)
FX5UJ-60M
400 mA (Supply capacity when 24 V DC service power supply is used for input circuit of the CPU module )
550 mA (Supply capacity when external power supply is used for input circuit of the CPU module)
*1
1 scan time
Power failure
detection time
SD8008
10 to 13 ms
Approx.
3 ms
t
*1
AC power supply
(AC detection)
t: time (as a guideline)
100 V AC: 0 ms to approximately 60 ms
200 V AC or higher: 0 ms to approximately 100 ms
SM8000:
SM8007:
SM8008:
RUN monitor
Momentary
power failure
detection
Power failure
detected
Summary of Contents for MELSEC iQ-F Series
Page 1: ...MELSEC iQ F FX5UJ User s Manual Hardware ...
Page 2: ......
Page 133: ...8 MAINTENANCE AND INSPECTION 8 2 Periodic Inspection 131 8 MEMO ...
Page 185: ...I 183 MEMO ...
Page 189: ......