56
4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
4.4
Limitation on Current Consumption
Power required for expansion adapters, expansion boards, and extension modules is supplied from the CPU module,
powered input/output module or extension power supply module. The number of extension devices that can be connected
must be determined from the capacity of the power supply.
Power supply check from the CPU module (current consumption
calculation)
Check if power can be supplied to extension devices with the power supply capacity of the CPU module.
• Current consumption calculation of the 5V DC power supply is not required.
• Current consumption calculation of the expansion board and expansion adapter is not required.
• For the extension module, current consumption calculation is not required when the total number of
occupied input/output points is 32 points or less, and up to two extension modules are connected. For the
subsequent extension modules, each module consumes 200 mA from the 24 V DC power supply.
Calculate following the procedure below.
1.
Check the power supply capacity of the CPU module used.
(
*1 Value when 24 V DC service power supply is used for input circuits. The power supply capacity differs when external power supply is
used for input circuit.
2.
Check the extension modules which requires current consumption calculation.
(
(
Page 44 Intelligent function module)
Type
Model
Type Model Power supply capacity (24 V DC service power
supply)
CPU module
FX5UJ-40MT/ES
400 mA
Type
Model
Current consumption (24 V DC power supply)
Expansion board
FX5-232-BD
(1)
Calculation is not required
Expansion adapter
FX5-232ADP
Calculation is not required
Output module
FX5-16EYT/ES
(2)
Calculation is not required (Output points: 16 points)
Input module
FX5-16EX/ES
Calculation is not required (Input points: 16 points)
Simple motion module
FX5-40SSC-S
(3)
200 mA
(1): Current consumption calculation of the expansion board and expansion adapter is not required.
(2): Current consumption calculation is not required when the total number of occupied input/output points is 32 points or less, and up to two extension modules
are connected. (In the above example, calculation is not required because
+
=32 points or less.)
(3): Each module of the subsequent expansion modules consumes 200 mA from the 24 V DC power supply.
Power supply from CPU module
CPU module
Ex.
Expansion
adapters
Expansion
board
Intelligent
module
Output
module
Input
module
Ex.
Ex.
Summary of Contents for MELSEC iQ-F Series
Page 1: ...MELSEC iQ F FX5UJ User s Manual Hardware ...
Page 2: ......
Page 133: ...8 MAINTENANCE AND INSPECTION 8 2 Periodic Inspection 131 8 MEMO ...
Page 185: ...I 183 MEMO ...
Page 189: ......