4 SYSTEM CONFIGURATION
4.4 Limitation on Current Consumption
59
4
Power supply check from extension power supply module
(current consumption calculation)
If the maximum number of CPU modules that can be connected is exceeded and further expansion modules are connected,
add an extension power supply module.
Check if power can be supplied to extension modules with the power supply capacity of the extension power supply module.
Calculate following the procedure below.
1.
Check the power supply capacity of the extension power supply module used.
(
Page 45 Extension power supply module)
If the ambient temperature exceeds 40
, use the extension power supply module at the following current
values within the derating range.
2.
Check the current consumption of the extension module.
(
(
Page 44 Intelligent function module)
*1 24 V DC power supply is supplied from the CPU module or powered input/output module.
Type
Model
Power supply capacity
5 V DC power supply
24 V DC service power supply
Extension power supply module
FX5-1PSU-5V
1200 mA
300 mA
Type
Model
Power supply capacity
5 V DC power supply
24 V DC service power supply
Input module
FX5-16EX/ES
100 mA
Output module
FX5-16EYR/ES
100 mA
125 mA
Simple motion module
FX5-40SSC-S
Network module
FX5-ASL-M
200 mA
CPU module
Power supply from extension power supply module
(Only the 5 V DC power supply for the input module is
supplied by the extension power supply module.)
Ex.
Expansion
adapters
Expansion
board
Output
module
Extension
power
supply
module
Input
module
Output
module
Intelligent
module
Intelligent
module
Ex.
Output current [mA]
Ambient
temperature [
]
Derating curve
In the case of FX5-1PSU-5V
1000
1200
800
55
40
300
200
5 V DC
24 V DC
Ex.