Check on limitations when using extension devices
Check the use of the extension devices.
■
Use of the module of extension cable type
(
Page 54 Modules of extension cable type)
■
Use of the bus conversion module
(
Page 54 Bus conversion module)
■
Connection of intelligent function modules
(
Page 54 Limitations on intelligent function modules)
Check of limitation on the number of input/output points
Check if the number of input/output points of the sample system configuration is within the limit range.
■
Number of input/output points
(
Page 58 Calculation of the number of input/output points)
Limitations
Judgement
When using the extension cable type module, FX5-CNV-IFC or FX5-C1PS-5V should be connected.
OK
Limitations
Judgment
FX3 extension modules are connected on the right side of the bus conversion module.
OK
FX5 extension modules are connected on the left side of the bus conversion module.
OK
Model
Limitations
Judgment
FX3U-128ASL-M
Only one module may be connected to the system.
Use together with the FX5-ASL-M is not possible.
OK
FX3U-64CCL
Only one module may be connected to the system.
When using the FX5-CCL-MS as the intelligent device station, it cannot be used together
with the FX5-CCL-MS.
OK
Type
Model
No. of input/output
points
No. of occupied input/
output points
CPU module
FX5UC-32MT/D
32 points
Expansion adapter
FX5-232ADP
Expansion adapter
FX5-485ADP
Input module
FX5-C16EX/D
16 points
Output module
FX5-C16EYT/D
16 points
Output module
FX5-C16EYT/D
16 points
Output module
FX5-C16EYT/D
16 points
Connector conversion module
FX5-CNV-IFC
Simple motion module
FX5-40SSC-S
8 points
Bus conversion module
FX5-CNV-BUS
8 points
Pulse output module
FX3U-1PG
8 points
Analog input module
FX3U-4AD
8 points
Temperature controller module
FX3U-4LC
8 points
AnyWireASLINK master module
FX3U-128ASL-M
8 points
CC-Link intelligent device module
FX3U-64CCL
8 points
+
96 points
≤
56 points
256 points
Number of input/output points
152 points
Calculation result
=
OK