2 SPECIFICATIONS
2.6 Performance Specifications
35
2
2.6
Performance Specifications
*1 Interrupt from the intelligent function module and high-speed pulse input/output module.
*2 The value listed above indicates the number of files stored in the root folder.
*3 Clock data is retained using the power accumulated in a large-capacity capacitor incorporated into the PLC. When voltage of the large-
capacity capacitor drops, clock data is no longer accurately retained. The retention period of a fully charged capacitor (electricity is
conducted across the PLC for at least 30 minutes) is 10 days (ambient temperature: 25
). How long the capacitor can hold the data
depends on the operating ambient temperature. When the operating ambient temperature is high, the holding period is short.
*4 It is possible to back up all devices in device (high-speed) area. When a battery is used, it is also possible to back up devices in device
(standard) area.
Item
Specifications
Control system
Stored-program repetitive operation
Input/output control system
Refresh system
(Direct access input/output allowed by specification of direct access input/output [DX, DY])
Programming
specifications
Programming language
Ladder diagram (LD), structured text (ST), function block diagram/ladder diagram (FBD/LD)
Programming extension function
Function block (FB), function (FUN), label programming (local/global)
Constant scan
0.2 to 2000 ms (can be set in 0.1 ms increments)
Fixed cycle interrupt
1 to 60000 ms (can be set in 1 ms increments)
Timer performance specifications
100 ms, 10 ms, 1 ms
No. of program executions
32
No. of FB files
16 (Up to 15 for user)
Operation
specifications
Execution type
Standby type, initial execution type, scan execution type, fixed-cycle execution type, event execution
type
Interrupt type
Internal timer interrupt, input interrupt, high-speed comparison match interrupt, interrupt by modules
Command
processing time
LD X0
34 ns
MOV D0 D1
34 ns
Memory
capacity
Program capacity
64 k steps
(128 kbytes, flash memory)
SD memory card
Memory card capacity (SD/SDHC memory card: Max. 16 Gbytes)
Device/label memory
120 kbytes
Data memory/standard ROM
5 Mbytes
Flash memory (Flash ROM) write count
Maximum 20000 times
File storage
capacity
Device/label memory
1
Data memory
P: No. of program files
FB: No. of FB files
P: 32, FB: 16
SD Memory Card
NZ1MEM-2GBSD: 511
NZ1MEM-4GBSD, NZ1MEM-8GBSD, NZ1MEM-16GBSD: 65534
Clock function
Display data
Year, month, day, hour, minute, second, day of week (leap year automatic detection)
Precision
Differences per month
45 sec./25
(TYP)
Power failure
retention
(clock data
Retention method
Large-capacity capacitor
Retention time
10 days (Ambient temperature: 25
)
No. of input/
output points
(1) No. of input/output points
256 points or less
(2) No. of remote I/O points
384 points or less
Total No. of points of (1) and (2)
512 points or less
Power failure
retention
(device)
Power failure retention capacity
Maximum 12 k word