- 33 -
3.Setting
3.14 Examples of Simple Settings
The following shows a simple setting example.
■
Setting Example
Model: ME96SSE-MB
Phase wire system : 3-phase 4-wire
Measuring element : A, V, W, PF
Input Voltage :220/380V
CT primary current : 200A
CT Secondary current:5A
frequency
:50Hz
MODBUS
®
RTU
:
address 1, baud rates 19.2kbps, parity even, stop bit 1
■
Setting Procedure
Items of which setting value need to be changed are indicated by .
Operation Mode
Set the setting menu number to "1" and then press S E T .
Setting menu
The factory default setting is "3-phase 4-wire," so just press SET.
Phase wire system
Setting is "P01," so just press SET.
Display pattern
The factory default setting is "No VT," so just press SET.
VT/direct voltage
selection
The factory default setting is "220/380V," so just press .
Direct voltage
The factory default setting is "5A," so just press SET.
CT secondary
current
Set to "200A" and then press SET.
CT primary
current
The factory default setting is "50Hz," so just press SET.
frequency
Set the setting menu number to "2" and then press SET .
Setting menu
SET
Note: For more details about setting contents, refer to pages 15 to 19.
SET
SET
SET
SET
SET
SET
SET
SET
Press
+
simultaneously for 2seconds
RESET
SET