- 25 -
3. Setting
3.6 Setting Menu 5:
Alarm Settings (Setting Upper/Lower Limit Alarm, Motor Starting Current
Mask Function.)
By using this setting for motor current monitoring delay time, it is possible to prevent
unnecessary maximum value updating and unnecessary alarms caused by the motor startup
current.
When this setting is not needed
→
Select "oFF" and press
,
and return to the Setting Menu
or go to menu 5.9(ME-4210-SS96)
When this setting is executed
→
Select "on" and press
, and go to (1) below.
(
1
)
Motor starting current value.
Set the value for detecting the motor starting current.
Setting range
Setting step (Note)
3 to 5 to 120 (%)
1%
* This is the percentage for the maximum scale value for
the current (±0 step).
(
2
)
Motor starting current delay time
After the motor starting current is detected, maximum value update
is not executed and an alarm is not generated for the delay time.
⑧
Motor starting current
delay time
oFF
on
1s
3s
5s
10s
15s
20s
30s
45s
1min
1.5min
2min
3min
4min
5min
SET
SET
SET
DISPLAY
It is possible to make the backlight to flicker when an alarm is generated.
⑦
Backlight flickers
during alarms
oFF
on
(Not flicker)
(Flicker)
Note: When all settings for
①
Alarm item 1
and
③
Alarm item 2 to 4
are set to "non," this setting will be skipped.
SET
DISPLAY
SET
According to the setting flow (page 14), save the changed
contents, or continue to the other setting menu.
Setting menu