FX2N-8AD Analog input block
Buffer Memory (BFM) 8
8-31
8.2.18
BFM #71 to BFM #78: Lower limit, error set value
BFM #81 to BFM #88: Upper limit, error set value
When using the upper/lower limit value detection function (BFM #22 b1), write the lower limit
value of each channel to BFM #71 to BFM #79 and the upper limit value of each channel to
BFM #81 to BFM #88.
When using the data addition function (BFM #22 b0) together, write the value added by the
addition data (BFM #61 to BFM #68) to BFM #71 to BFM #78 and BFM #81 to BFM #88.
Setting range
The setting range varies depending on the setting of the input mode (BFM #0, BFM #1).
The table below shows the setting range in each input mode. Write the set value in a digital
value.
Table 8.10: Setting range
Input mode (BFM #0, BFM #1)
Setting range
Initial value
Lower
limit
Upper
limit
0: Voltage input mode (-10 to +10 V), resolution 10 V x 1/16,000
-16384 to 16383 -16384
16383
1: Voltage input mode (-10 to +10 V), resolution 10 V x 1/4,000
-4096 to 4095
-4096
4095
2: Voltage input mode, analog value direct display (-10,000 to +10,000) -10200 to 10200 -10200
10200
3: Current input mode (4 to 20 mA), resolution 20 mA x 1/8,000
-1 to 8191
-1
8191
4: Current input mode (4 to 20 mA), resolution 20 mA x 1/4,000
-1 to 4095
-1
4095
5: Current input mode, analog value direct display (4,000 to 20,000) 3999 to 20400
3999
20400
6: Current input mode (-20 to +20 mA), resolution 20 mA x 1/8,000
-8192 to 8191
-8192
8191
Summary of Contents for FX2N-8AD
Page 4: ...FX2N 8AD Analog input block ii ...
Page 8: ...FX2N 8AD Analog input block vi ...
Page 14: ...FX2N 8AD Analog input block External Dimensions 2 2 2 MEMO ...
Page 16: ...FX2N 8AD Analog input block Part Name 3 3 2 MEMO ...
Page 20: ...FX2N 8AD Analog input block Connection to PLC 5 5 2 MEMO ...
Page 24: ...FX2N 8AD Analog input block Wiring 6 6 4 MEMO ...
Page 70: ...FX2N 8AD Analog input block Buffer Memory BFM 8 8 42 MEMO ...
Page 84: ...FX2N 8AD Analog input block Example program 10 10 6 MEMO ...
Page 87: ......