FX2N-8AD Analog input block
Buffer Memory (BFM) 8
8-25
8.2.12
BFM #29: Error status
The error information is assigned to each bit of BFM #29.
Table 8.6: Bit assignment in BFM #29
Bit
No.
Assignment
Description
b0
Error detected
b0 is ON while either one among b1 to b4 is ON.
b1
Offset/gain set value error
Offset/gain value is outside setting range.
Set a correct value.
b2
Power error
24 V power is not normally supplied.
Check wiring and supply voltage.
b3
Hardware error
FX
2N
-8AD may have failed.
Contact Mitsubishi Electric System Service nearest to you.
b4
A/D conversion value error
A/D conversion value is abnormal.
Using scale over data (BFM #28), check channel in which error has
occurred.
b5
Thermocouple being
warmed up
This bit is ON for 20 minutes after power is turned on.
b6
BFM read/write disabled
This bit is ON during input characteristics change processing.
While this bit is ON, correct A/D data cannot be read from or written
to BFM.
b7
⎯
⎯
b8
Set value error detected
This bit is ON while either bit among b9 to b15 is ON.
Summary of Contents for FX2N-8AD
Page 4: ...FX2N 8AD Analog input block ii ...
Page 8: ...FX2N 8AD Analog input block vi ...
Page 14: ...FX2N 8AD Analog input block External Dimensions 2 2 2 MEMO ...
Page 16: ...FX2N 8AD Analog input block Part Name 3 3 2 MEMO ...
Page 20: ...FX2N 8AD Analog input block Connection to PLC 5 5 2 MEMO ...
Page 24: ...FX2N 8AD Analog input block Wiring 6 6 4 MEMO ...
Page 70: ...FX2N 8AD Analog input block Buffer Memory BFM 8 8 42 MEMO ...
Page 84: ...FX2N 8AD Analog input block Example program 10 10 6 MEMO ...
Page 87: ......