FX2N-8AD Analog input block
Example program 10
10-3
Figure 10.1:Example program
M8002
K0
K0
H3300
K1
K0
K1
HFF99
K1
K0
K22
H0002
K1
K0
K10
D0
K6
K0
K26
K4M0
K1
Specifies the input mode of
CH1 to CH4.
Specifies the input mode of
CH5 to CH8.
Enables the upper/lower limit value detection function.
Reads the channel data from CH1 to CH6.
(CH1
→
D0, CH2
→
D1,
.....
CH6
→
D5)
Reads the upper/lower limit value error status.
(M0 to M15)
FNC 79
TO
FNC 79
TO
FNC 79
TO
FNC 78
FROM
FNC 78
FROM
K0
K28 K4M20
K1
K0
K29
D6
K1
FNC 78
FROM
FNC 78
FROM
K0
K99
H0003
K1
K0
K28
K0
K1
P
FNC 79
TO
X001
Clear of upper/
lower limit value
error
X002
Clear of scale
over error
RUN monitor
Reads the scale over status.
(M20 to M25)
Reads the error status.
(BFM #29
→
D6)
Clears the upper/lower limit value error.
Clears the scale over error.
P
FNC 79
TO
TO
K50
M8000
T0
Initial pulse
P
Stand by for five seconds.
As for the changed input
mode, the power failure
maintenance is done by
EEPROM.
The change of program in the
input mode and stand by for
five seconds can be omitted.
At use the input mode
memorized in EEPROM.
Summary of Contents for FX2N-8AD
Page 4: ...FX2N 8AD Analog input block ii ...
Page 8: ...FX2N 8AD Analog input block vi ...
Page 14: ...FX2N 8AD Analog input block External Dimensions 2 2 2 MEMO ...
Page 16: ...FX2N 8AD Analog input block Part Name 3 3 2 MEMO ...
Page 20: ...FX2N 8AD Analog input block Connection to PLC 5 5 2 MEMO ...
Page 24: ...FX2N 8AD Analog input block Wiring 6 6 4 MEMO ...
Page 70: ...FX2N 8AD Analog input block Buffer Memory BFM 8 8 42 MEMO ...
Page 84: ...FX2N 8AD Analog input block Example program 10 10 6 MEMO ...
Page 87: ......