FX2N-8AD Analog input block
Buffer Memory (BFM) 8
8-28
8.2.16
BFM #41 to BFM #48: Offset data
BFM #51 to BFM #58: Gain data
Offset data : Analog input value when the digital value is "0"
Gain data : Analog input value when the digital value is as shown below
(The digital value varies depending on the setting of the input mode.)
Standard digital value of offset and gain in each input mode
(A number in the input mode column indicates a value set in BFM #0, BFM #1.)
•
You can set the offset data and the gain data for each channel.
•
Write the set value in the unit of "mV" for voltage input or "
µ
A" for current input.
•
You cannot change the input characteristics in the analog value direct display mode and the
thermocouple input mode. (Even if you write a numeric value, it is ignored.)
Table 8.7: Standard digital value
Input mode
(BFM #0, BFM #1)
0
1
2
3
4
5
6
7
8
Standard offset
value
0
0
Unchange-
able
0
0
Unchange-
able
0
0
Unchange-
able
Standard gain
value
8000 2000
Unchange-
able
8000 4000
Unchange-
able
8000 4000
Unchange-
able
Summary of Contents for FX2N-8AD
Page 4: ...FX2N 8AD Analog input block ii ...
Page 8: ...FX2N 8AD Analog input block vi ...
Page 14: ...FX2N 8AD Analog input block External Dimensions 2 2 2 MEMO ...
Page 16: ...FX2N 8AD Analog input block Part Name 3 3 2 MEMO ...
Page 20: ...FX2N 8AD Analog input block Connection to PLC 5 5 2 MEMO ...
Page 24: ...FX2N 8AD Analog input block Wiring 6 6 4 MEMO ...
Page 70: ...FX2N 8AD Analog input block Buffer Memory BFM 8 8 42 MEMO ...
Page 84: ...FX2N 8AD Analog input block Example program 10 10 6 MEMO ...
Page 87: ......