FX2N-8AD Analog input block
Buffer Memory (BFM) 8
8-32
7: Current input mode (-20 to +20 mA), resolution 20 mA x 1/4,000
-4096 to 4095
-4096
4095
8: Current input mode, analog value direct display (-20,000 to +20,000) -20400 to 20400 -20400
20400
9: Thermocouple input mode (K type), Celsius display
-1000 to 12000
-1000
12000
A: Thermocouple input mode (J type), Celsius display
-1000 to 6000
-1000
6000
B: Thermocouple input mode (T type), Celsius display
-1000 to 3500
-1000
3500
C: Thermocouple input mode (K type), Farenheit display
-1480 to 21920
-1480
21920
D: Thermocouple input mode (J type), Farenheit display
-1480 to 11120
-1480
11120
E: Thermocouple input mode (T type), Farenheit display
-1480 to 6620
-1480
6620
F: Channel unusable
Invalid
-1
1
Table 8.10: Setting range
Input mode (BFM #0, BFM #1)
Setting range
Initial value
Lower
limit
Upper
limit