![Mitsubishi Electric FX2N-16E series User Manual Download Page 37](http://html.mh-extra.com/html/mitsubishi-electric/fx2n-16e-series/fx2n-16e-series_user-manual_238876037.webp)
2 Features and Part Names
2.2 Names and Functions of Parts
31
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
1
Introduc
tion
2
Features an
d
Part Nam
es
3
Produc
t
Introducti
on
4
Specifi
cations
5
Ve
rsi
on and
Peri
pheral
De
vice
s
6
Sy
stem
Confi
gurati
on
7
Input/Output
N
os.,
Unit N
os.
8
Ins
tallati
on
9
Preparati
on
and
Power Suppl
y
Wi
rin
g
10
Input W
iring
2.2
Names and Functions of Parts
2.2.1
Front Panel
Factory default configuration (standard)
[1] Peripheral device connecting
connector cover
The peripheral device connector, variable analog potentiometers and RUN/STOP switch
are located under this cover.
[2] Terminal names
The signal names for power supply, input and output terminals are shown.
shows a function grounding terminal.
[3] Top cover (S)
(40points, 60points type only)
Mount the expansion board and memory cassette under this cover.
[4] Top cover
Mount the expansion board, display module, memory cassette and battery under this
cover.
[5] Terminal block covers
The covers can be opened for wiring.
Keep the covers closed while the PLC is running (the unit power is on).
[6] Input display LEDs (red)
When an input terminal (X000 or more) is turned on, the corresponding LED lights.
[7] Extension device connecting
connector cover
Connect the extension cables of input/output powered extension unit/block or special
function block to the extension device connecting connectors under this cover.
FX
3U
Series extension devices and FX
2N
Series extension devices can be connected.
→
For details on the extension devices, refer to
Chapter 15, Chapter 16, Chapter 17 and Section 18.1.
[8] Operation status display LEDs
The operation status of the PLC can be checked with the LEDs.
The LEDs turn off, light and flash according to the following table.
→
For details on the operation status, refer to Section 14.5.
[9] Output display LEDs (red)
When an output terminal (Y000 or more) is turned on, the corresponding LED lights.
[10] Model name (abbreviation)
The model name of the main unit is indicated.
Check the nameplate on the right side for the model name.
[11] DIN rail mounting hooks
The main unit can be installed on DIN46277 rail (35mm (1.38") wide).
[12] The year and month of production
The year and month of production of the main unit is indicated.
→
For details on the year and month of production, refer to Subsection 5.1.2.
[6]
[2]
[1]
[5]
[4]
[3]
[9]
[11]
[8]
[7]
[10]
[12]
LED name
Display color
Description
POW
Green
On while power is on the PLC.
RUN
Green
On while the PLC is running.
ERR
Red
Flashing when a program error occurs.
Red
Lights when a CPU error occurs.
ALM
Red
Lights when the battery voltage drops.
(When the optional battery is used)