15 Input/Output Powered Extension Units
15.5 FX2N-32ER, FX2N-48ER, FX2N-48ER-D
238
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
3. Output specifications (relay output type)
15.5.2 External dimensions
FX
2N
-32ER
Item
FX
2N
-32ER
FX
2N
-48ER, FX
2N
-48ER-D
Output Points
16 points
24 points
Connection type
Removable terminal block (M3 screw)
Output unit
Relay
External power supply
250V AC/30V DC or less
Output circuit insulation
Mechanical insulation
Indication of output operation
When power is applied to relay coil, LED is lit.
Max. load
Resistance load
2A/point
The total load current per common terminal
should be the following value.
•
8 output points/common terminal: 8A or less
2A/point
The total load current per common terminal
should be the following value.
•
4 output points/common terminal: 8A or less
•
8 output points/common terminal: 8A or less
Inductive load
80VA
→
For the product life, refer to Subsection 14.4.3.
→
For cautions on external wiring, refer to Subsection 12.1.3.
Open circuit leakage current
-
Min. load
5V DC, 2mA (reference value)
Response time
OFF ON
Approx. 10ms
ON OFF
Approx. 10ms
Output circuit configuration
External
power supply
Load
Fuse
Y
COM
DC power
supply
Fuse
Y
COM
A common number applies to the of [COM ].
150 (5.91")
140 (5.52") (mounting hole pitch)
80 (3.15")
(mounting hole pitch)
90 (3.55")
9 (0.36")
Unit : mm (inches)
87 (3.43")
2- 4.5 mounting holes