10 Input Wiring Procedures
10.4 Input Interruption (I00
to I50
)
155
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
1
Introduc
tion
2
Features an
d
Part Nam
es
3
Produc
t
Introducti
on
4
Specifi
cations
5
Ve
rsi
on and
Peri
pheral
De
vice
s
6
Sy
stem
Confi
gurati
on
7
Input/Output
N
os.,
Unit N
os.
8
Ins
tallati
on
9
Preparati
on
and
Power Suppl
y
Wi
rin
g
10
Input W
iring
10.4
Input Interruption (I00
to I50
)
The PLC (main unit) is provided with an input interruption function and has six interruption input points.
Make sure that the ON duration or OFF duration of interruption input signals is 10 s or more (X000, X001,
X003 and X004) or 50 s or more (X002 and X005).
→
For details on programming, refer to the programming manual.
10.4.1 Allocation of pointers to input numbers (input signal ON/OFF duration)
10.4.2 Cautions for input interruption
1. Non-overlap of input numbers
The input terminals X000 to X005 can be used for high-speed counter, input interruption, pulse catch, SPD,
ZRN and DSZR instructions and general-purpose inputs.
Take care not to overlap the input numbers.
2. Cautions in wiring
It is recommended to use shielded twisted-pair cables for connection cables.
Input
number
Interrupt pointer
Interrupt disable control
ON or OFF duration of input signal
Interruption on
leading edge
Interruption on
trailing edge
X000
I001
I000
M8050
10 s or more
X001
I101
I100
M8051
X002
I201
I200
M8052
50 s or more
X003
I301
I300
M8053
10 s or more
X004
I401
I400
M8054
X005
I501
I500
M8055
50 s or more