12 Output Wiring Procedures
12.2 External Wiring of Transistor Output (Sink/Source) Type
179
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
11
H
igh-Speed
C
ounters
12
O
utpu
t Wi
ring
13
Wi
ring for
Va
rious U
ses
14
Te
st R
un,
M
ain
tenanc
e,
Troub
le
shooting
15
Input/O
utput
Pow
ere
d
Extens
ion U
nit
s
16
Input/Output
Ex
tension
Blocks
17
Extensi
on
Pow
er Suppl
y
Un
it
18
O
ther Ex
tensi
on
Un
its
an
d
O
pti
ons
19
Displ
ay
Modul
e
20
Te
rmi
nal Block
12.2.2 Handling of transistor output
1. Output terminals
One, 4 or 8 transistor output points are covered by one common terminal.
Sink output
Connect each COM (number) terminal to the minus side of
the load power supply.
The COM terminals are not connected internally.
Source output
Connect each +V (number) terminal to the plus side of the
load power supply.
The +V terminals are not connected internally.
2. External power supply
For driving the load, use a smoothing power supply of 5-30 V DC that can output current two or more times
the rated current of the fuse connected to the load circuit.
3. Insulation of circuit
The internal circuit of the PLC and the output transistor are insulated with a photocoupler.
The common blocks are separated from one another.
4. Display of operation
Operation indicator LEDs are built into the main unit and output extension blocks, and turn ON when
photocouplers are actuated.
PLC
Load
DC power
supply
Fuse
Y 0
COM1
Load
Fuse
COM2
Sink output type
DC power
supply
Y 1
Y 5
Y 4
PLC
Load
DC power
supply
Fuse
+V0
Load
DC power
supply
Fuse
+V1
Source output type
Y 0
Y 1
Y 5
Y 4