![Mitsubishi Electric FX2N-16E series User Manual Download Page 240](http://html.mh-extra.com/html/mitsubishi-electric/fx2n-16e-series/fx2n-16e-series_user-manual_238876240.webp)
15 Input/Output Powered Extension Units
15.4 FX2N-32ET-ESS/UL, FX2N-48ET-ESS/UL, FX2N-48ET-DSS
234
FX
3G
Series Programmable Controllers
User's Manual - Hardware Edition
15.4
FX
2N
-32ET-ESS/UL, FX
2N
-48ET-ESS/UL, FX
2N
-48ET-DSS
15.4.1 Product specifications
The generic specifications are the same as those for the main unit.
→
Refer to Section 4.1 for generic specifications.
For external wiring, refer to the following chapters.
→
Refer to Chapter 9 for power supply wiring.
→
Refer to Chapter 10 for input wiring.
→
Refer to Chapter 12 for output wiring.
1. Power supply specifications
→
For the power supply specifications, refer to Section 15.2.
2. Input specifications (for sink input and source input)
*1.
Do not connect with 0V and 24V terminals.
Item
FX
2N
-32ET-ESS/UL
FX
2N
-48ET-ESS/UL, FX
2N
-48ET-DSS
Input points
16 points
24 points
Connection type
Removable terminal block (M3 screw)
Input form
sink/source
Input signal voltage
AC power supply type: 24V DC 10%
DC power supply type: 24V DC +20%, -30%
Input signal current
5mA/24V DC
Input impedance
4.3 k
Input response
time
Input ON current
3.5mA or more/24V DC
Input OFF current
1.5mA or less
Input response time
Approx. 10ms
Input signal form (Input sensor form)
No-voltage contact input
Sink: NPN open collector transistor
Source: PNP open collector transistor
Input circuit insulation
Photo-coupler insulation
Indication of input operation
LED on panel lights when input.
Input circuit diagram
•
AC power supply type
•
DC power supply type
24V
N
L
100 to 240V AC
Fuse
X
S/S
0V
Source input wiring
24V
N
L
100 to 240V AC
Fuse
X
S/S
0V
Sink input wiring
4.3k
4.3k
24V
Fuse
X
S/S
0V
Source input wiring
24V
Fuse
X
S/S
0V
Sink input wiring
*1
*1
4.3k
Ω
4.3k
Ω
24V
DC
24V
DC