43
2. INSTALLATION AND WIRING
2.6 Control circuit
1
2
3
4
5
6
7
8
9
10
1.
Strip the signal wires as shown below. If too much of the wire is stripped, a short circuit may occur with neighboring
wires. If not enough of the wire is stripped, wires may become loose and fall out.
Twist the stripped end of wires to prevent them from fraying. Do not solder it.
2.
Crimp the terminals on the wire.
Insert wires to the crimp terminal, and check that the wires come out for about 0 to 0.5 mm from a sleeve.
Check the condition of the crimp terminals after crimping. Do not use the crimp terminals of which the crimping is
inappropriate, or the face is damaged.
Crimp terminals commercially available (as of January 2017)
• Phoenix Contact Co., Ltd.
*1
A ferrule terminal with an insulation sleeve compatible with the MTW wire which has a thick wire insulation.
*2
Applicable for terminals A1, B1, C1.
• NICHIFU Co., Ltd.
Wire strip length
Wire gauge
(mm
2
)
Ferrule part No.
Crimping tool
model No.
With insulation sleeve
Without insulation
sleeve
For UL wire
0.3
AI 0,34-10TQ
—
—
CRIMPFOX 6
0.5
AI 0,5-10WH
—
AI 0,5-10WH-GB
0.75
AI 0,75-10GY
A 0,75-10
AI 0,75-10GY-GB
1
AI 1-10RD
A 1-10
AI 1-10RD/1000GB
1.25, 1.5
AI 1, 5-10BK
A 1, 5-10
AI 1,5-10BK/1000GB
0.75 (two-wire
product)
AI-TWIN 2×0,75-10GY
—
—
Wire gauge
(mm
2
)
Blade terminal part
No.
Insulation cap part No.
Crimping tool product
number
0.3 to 0.75
BT 0.75-11
VC 0.75
NH 69
3.
Insert the wires into a socket.
When using single wire or stranded wire without crimp
terminal, push an open/close button all the way down with a
flathead screw driver, and insert the wire.
Crumpled tip
Wires are not inserted
into the sleeve
Unstranded
wires
Damaged
Wire
W
ire
Sl
eeve
Sl
ee
ve
0 to 0.5m
m (0.02 inch)
0
to
0
.5
m
m
(0
.0
2
inc
h)
Flathead screwdriver
Open/close button