28
2. INSTALLATION AND WIRING
2.4 Terminal connection diagrams
2.4
Terminal connection diagrams
When the sink logic is selected
*1
When using a separate power supply for the control circuit, remove the jumpers connected to terminals R1/L11 and S1/L21.
*2
To use the power failure time deceleration-to-stop function, remove the jumpers connected to terminals R1/L11 and S1/L21, and connect terminal
R1/L11 and the terminal P/+ bus bar and terminal S1/L21 and the terminal N/- bus bar. Pass wires between the converter unit and the inverter
and through the rubber bush on the side face of the converter unit to the terminals inside. (Refer to
for details.)
*3
The function of these terminals can be changed using the Input terminal function selection (
Pr.178, Pr.187, Pr.189
).
*4
The function of these terminals can be changed using the Output terminal function selection (
Pr.195
).
*5
The function of these terminals can be changed using the Output terminal function selection (
Pr.190 to Pr.194
).
*6
For manufacturer. Do not use.
*7
To use the RDA signal of the converter unit, select the normally-closed contact input specification for the input logic of the MRS signal or X10
signal of the inverter.
To use the RDB signal of the converter unit, select the normally-open contact input specification for the input logic of the MRS signal or X10 signal
of the inverter.
(For changing the input logic, refer to the Instruction Manual of the inverter.)
Three-phase
AC power
supply
MCCB
Jumper
R/L1
S/L2
T/L3
R1/L11
S1/L21
PC
24VDC power supply
(Common for external power supply transistor)
Reset
External thermal relay input
Contact input
Inverter operation enable
(NO contact)
Inverter operation enable
(NC contact)
Inverter reset
Instantaneous
power failure
Cooling fan fault
Open collector output common
Sink/source common
Control input signals
(No voltage input allowed)
∗3
Relay output
(Fault output)
C1
B1
A1
Earth
(Ground)
Open collector output
∗5
Contact input common
Main circuit terminal
Control circuit terminal
MC
Main circuit
Relay output
∗4
TXD+
Terminating
resistor
TXD-
RXD+
RXD-
GND
(SG)
Data transmission
GND
RS-485 terminals
PU
connector
SINK
SOURCE
RES
OH
RDI
SD
RDA
RDB
RSO
MRS
(X10)
IPF
FAN
SE
Data reception
VCC
5V (Permissible load
current 100mA)
Sink logic
Inverter
∗1,∗2
∗7
N/-
P/+
Control circuit
DC reactor
+24
24V external power
supply input
Common terminal
SD
RES
SD
EMC filter
ON/OFF
connecter
ON
OFF
ON
OFF
USB
mini B
connector
∗6
N/-
P/+
88R
88S
∗6
Plug-in
option
connector
1
∗6
24V
Inrush current
limit circuit