90
(2) Specification of the FR-E5ND (FR-E500-KND) compatible mode
The table below shows the differences between the FR-E5ND (FR-E500-KND) compatible mode and the
normal mode.
Refer to the FR-E5ND and FR-E500-KND manuals for details of each function of compatible mode
Class
ID
Instance
ID
Attribute
ID
Name
FR-E5ND
(FR-E500-KND)
Compatible Mode
Normal Mode
(FR-A7ND)
Refer to
page
0x03
1
1
Node address
setting (MAC ID)
Available by re-powering on
after writing to MAC ID
Available soon after writing to
MAC ID
0x28
1
6
Rated current
(Pr.9)
0.01A increments
0.1A increments
0x28
1
7
Rated voltage
Read from/write to
Pr.83
Read from/write to
Pr.19
0.1V increments
1V increments
0x28
1
9
Rated frequency
(Pr.84)
{
×
0x28
1
15
Base speed
(Pr.3)
{
×
0x2A
1
7
SpeedActual
(actual speed)
When
Pr.37
= "0", the number
of motor poles is always 4 and
the frequency is changed to
the speed.
When
Pr.37
≠
"0", the speed is
as set in
Pr.37
.
The number of motor poles is
always 4 and the frequency is
changed to the speed
regardless of the
Pr.37
setting.
0x2A
1
8
SpeedRef
(speed setting value)
0x2A
1
20
LowSpdLimit
(minimum frequency)
(Pr. 2)
0x2A
1
21
HighSpdLimit
(maximum frequency)
(Pr. 1)
Speed setting/monitor of the polling I/O
(
{
: Available,
×
: Not available)