7.11 Class 0x80 (Extended Object IV)
7.11.1 Class 0x80 Instance 1
Inverter monitored value can be read. Refer to
the Instruction Manual of the inverter
for details of each
monitor.
(1) Attribute
*1
Input terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0,
⎯
: undetermined value)
*2
Output terminal monitor details (when the terminal is ON: 1, when the terminal is OFF: 0,
⎯
: undetermined value)
Attribute
ID
Access
Description (Increments)
11
Get
Output frequency
(0.01Hz)
12
Get
Output current
(0.01A)
13
Get
Output voltage
(0.1V)
15
Get
Frequency setting
(0.01Hz)
17
Get
Motor torque
(0.1%)
18
Get
Converter output voltage
(0.1V)
19
Get
Regenerative brake duty
(0.1%)
20
Get
Electronic thermal relay function
load factor
(0.1%)
21
Get
Output current peak value
(0.01A)
22
Get
Converter output voltage peak
value
(0.1V)
24
Get
Output power
(0.01kW)
25
Get
Input terminal status
26
Get
Output terminal status
30
Get
Cumulative energization time
(1h)
33
Get
Actual operation time
(1h)
34
Get
Motor load factor
(0.1%)
35
Get
Cumulative power
(1kWh)
62
Get
PID set point
(0.1%)
63
Get
PID measured value
(0.1%)
64
Get
PID deviation
(0.1%)
71
Get
Motor thermal load factor
(0.1%)
72
Get
Inverter thermal load factor
(0.1%)
73
Get
Cumulative power 2
(0.01kWh)
Attribute
ID
Access
Description (Increments)
b15
b0
⎯
⎯
⎯
⎯
⎯
RES
⎯
MRS
⎯
RH
RM
RL
⎯
⎯
STR
STF
b15
b0
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
⎯
ABC
FU
⎯
⎯
⎯
RUN