52
OBJECT MAP
7.3.1 Output Instance 20/Input Instance 70
1. Output Instance 20 (Master
→
inverter)
When using Output Instance 20, set Input Instance to 70.
[Output Instance 20 details]
Byte
Bit7
Bit6
Bit5
Bit4
Bit3
Bit2
Bit1
Bit0
0
⎯
⎯
⎯
⎯
⎯
Fault
Reset
⎯
Run Fwd
1
⎯
2
Speed reference (low byte)
3
Speed reference (high byte)
Byte0
Bit0
Run Fwd
Forward rotation signal
(0:forward rotation off, 1:forward rotation on)
Bit2
Fault Reset
Reset request at an error occurrence
Valid only at in inverter trip
(0:no function, 1:fault reset request)
Byte2
Byte3
Speed Ref
Speed reference (r/min)
(Refer to
page 42
for conversion formula of speed and frequency. )