75
OBJECT MAP
z
Run command (Set)
Bit
Signal
Description
0
⎯
(Not used)
(Always 0)
1
Forward rotation command
*2
0 : Stop command
1 : Forward rotation start
A starting command is input to the
inverter when the signal turns on.
A stop command is given when both
signals turn on simultaneously.
2
Reverse rotation command
*2
0 : Stop command
1 : Reverse rotation start
3
High speed operation command
(terminal RH function)
*1
Functions assigned to terminal RH, RM and RL are activated.
4
Middle speed operation command
(terminal RM function)
*1
5
Low speed operation command
(terminal RL function)
*1
6
⎯
(Not used)
(Always 0)
7
Second function selection
(RT signal)
*3
1 : Second function is selected.
8
Terminal 4 input selection
(AU signal)
*3
1 : Terminal 4 input is the main speed.
9
⎯
(Not used)
(Always 0)
10
Output stop
(terminal MRS function)
*1
Functions assigned to terminal MRS are activated.
11
⎯
(Not used)
(Always 0)
12
Reset (terminal RES function)
*1
Functions assigned to terminal RES are activated.
13 to 15
⎯
(Not used)
(Always 0)