17
WIRING
(3) Loosen the terminal screw and insert the cable into the terminal
according to the terminal arrignment.
Tighten each cable with fixing screws to the recommended tightening torque.
(4) Connect the terminal block to the connector for communication of the communication option mounted
on the inverter.
Screw Size Tightening Torque Cable Size
Screwdriver
M3
0.5N•m to
0.6N•m
0.3mm
2
to
0.75mm
2
Small flat-blade
screwdriver
(Tip thickness: 0.4mm/tip
width: 2.5mm)
CAUTION
• Undertightening can cause cable disconnection or malfunction. Overtightening can cause a short
circuit or malfunction due to damage to the screw or unit.
V- (black)
CAN- (blue)
Shielded cable
CAN+ (white)
V+ (red)
Terminal layout