71
OBJECT MAP
9
Get
CurrentActual
(actual current)
0 to 3276.7A
The output current is monitored in 0.1A
increments.
15
Get
PowerActual
(actual power)
0 to 65535W
Output power is monitored in 1W increments.
17
Get
OutputVoltage
(output voltage)
0 to 32767V
The output voltage is monitored in 1V
increments.
18
Get/Set
AccelTime
(acceleration time)
0 to 65535ms
Acceleration time =
Pr. 7
× (
Pr. 1
/
Pr. 20
)
Set the increments in ms regardless of the
Pr. 21
setting.
19
Get/Set
DecelTime
(deceleration time)
0 to 65535ms
Acceleration time =
Pr. 8
× (
Pr. 1
/
Pr. 20
)
Set the increments in ms regardless of the
Pr. 21
setting.
20
Get/Set
LowSpdLimit
(minimum frequency)
(Pr. 2)
0 to 65535r/min
Minimum speed (1r/min increments)
(Refer to
page 42
for conversion formula of
speed and frequency.)
21
Get/Set
HighSpdLimit
(maximum frequency)
(Pr. 1)
0 to 65535r/min
Maximum speed (1r/min increments)
(Refer to
page 42
for conversion formula of
speed and frequency.)
29
Get
RefFromNet
(speed command
source monitor)
0
Other than DeviceNet communication operation
1
DeviceNet communication operation
Class 0x2A Instance 1
Attribute
ID
Access
Name
Range
Description